| 2017-03-23 11:37:21 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | 1. IT IS SUGGESTED THAT REVISIONS A THROUGH D, PLAN |
| | CHANGES PRIOR TO PERMIT ISSUANCE, CLOUDS BE REMOVED |
| | FROM THE PLAN. BEFORE REMOVING CLOUDS, SEE OTHER |
| | COMMENTS AND ENSURE THAT ALL REVISIONS ARE CORRECTLY |
| | MARKED. SOME CLOUDS SHOW CHANGES MADE BEFORE PERMIT |
| | ISSUANCE, BUT THE CHANGES WERE NOT ON THE ISSUED SET |
| | AND THEREFORE REQUIRE REVIEW. IT IS NOT CLEAR WHETHER |
| | THE CLOUD IS NUMBERED IN CORRECTLY OR IF THE PAGES |
| | SUBMITTED FOR PERMIT WERE NOT CURRENT. |
| | |
| | 2. LS0.1 AND OTHER SHEETS, A DIMENSION "22 MIN" WAS |
| | ADDED; NOT CLEAR WHAT THIS IS, CLARIFY OR REVISE. IT IS |
| | NOT CLEAR WHY THE DIMENSION OF 22 TO THE CENTER OF |
| | CORRIDORS WHICH ARE OVER 5' IS NECESSARY. IS APPLICANT |
| | PROPOSING TO REDUCE THE WIDTH OF THE CORRIDORS? IF THIS |
| | IS THE CASE, INCLUDE THE TOTAL WIDTH FOR EACH CORRIDOR, |
| | EACH FLOOR. A COMPLETE PLAN REVIEW CANNOT BE DONE AT |
| | THIS TIME DUE TO LACK OF INFORMATION. FBC CHAPTER 10. |
| | |
| | 3. LS0.1 AND OTHER SHEETS, BOTTOM LEFT CORNER OF |
| | PARKING GARAGE, A RAMP IS SHOWN FOR ACCESS TO FIRST |
| | LEVEL, BUT LACKS A STAIR. SEE FBC A 405.2, ADVISORY, |
| | THE ADDITIONAL DISTANCE CRATED BY A RAMP CAUSES A |
| | HARDSHIP FOR SOME PEOPLE AND A STAIR IS RECOMMENDED. |
| | |
| | 4. LS0.1, A3 OCCUPANT LOADS AT THE POOL AREA WERE |
| | REMOVED, RESTORE OCCUPANT LOADS, FBC CHAPTER 10. |
| | |
| | 5. LS0.3, OTHER LEVELS AND UNITS, BALCONIES WERE ADDED |
| | TO C2, NOT CLOUDED. TO EXPEDITE PLAN REVIEW, CLOUD ALL |
| | CHANGES, FBC 107. |
| | |
| | 6. LS0.4, AMENITY DECK 4TH FLOOR IS CLOUDED BUT IT IS |
| | NOT CLEAR WHAT CHANGED. THIS SHEET IS NAMED "LEVELS |
| | 4-7" IN PROJECTDOX BUT THE GRAPHIC TITLE IS 4TH FLOOR, |
| | CORRELATE AND COORDINATE NAME CHANGE WITH LIBRARIANS. |
| | |
| | AS IT IS NOT CLEAR WHETHER THIS SHEET IS FOR FLOORS |
| | 4-7, OR 4TH FLOOR ONLY. BUILDING REVISIONS WERE |
| | SUBMITTED FOR THE OTHER FLOORS, BUT LIFE SAFETY PLANS |
| | WERE SUBMITTED FOR 1-4 (1-7?) ONLY. |
| | |
| | 7. A2.7 SHOWS A NEW REVISION D WHICH WAS NOT ON THE |
| | ISSUED PERMIT SET (BUT IS NOTED AS PLAN REVIEW |
| | COMMENTS). CLARIFY WHAT CHANGED OR REMOVE. THIS MAY |
| | AFFECT OTHER SHEETS; NOT EACH SHEET WAS VERIFIED FOR |
| | REVISIONS REVIEWED. |
| | |
| | 8. AREA ABOVE STAIR #4, 121 ADDED AND 170 REMOVED, NOT |
| | CLEAR WHAT CHANGED. |
| | |
| | 9. A4.2.A, A4.5.A, OTHER SHEETS, SOME BALCONIES ARE |
| | NARROWER THAN 5'. IT IS NOT CLEAR HOW THE REQUIREMENT |
| | FOR THIS TO BE ADAPTABLE IS MET, FBC A FAIR HOUSING |
| | REQUIREMENT 4. |
| | |
| | 10. A5.1.6, THE CLOUD AT DETAIL C CLUB HOUSE ROOF DECK |
| | KITCHEN IS LABELED DELTA C, BUT DOES NOT APPEAR TO BE |
| | ON THE ISSUED SET. UNABLE TO LOCATE A DELTA 1. |
| | |
| | 11. NOT CLEAR WHAT WAS MODIFIED AT THE CLUBHOUSE, SHEET |
| | A5.2.1 AND OTHER PAGES, FBC 107. |
| | |
| | 12. A5.4 RES LOBBY 114, APPEARS THAT A DOOR WAS REMOVED |
| | FROM THE DOOR SCHEDULE AND NOW REFERS TO STOREFRONT, |
| | CLARIFY CHANGE AND HOW THIS AFFECTS EXITING. |
| | |
| | 13. A5.4 AND ELEVATIONS, APPEARS THAT A DOOR WAS |
| | REMOVED FROM THE BRIDGE, CLARIFY CHANGE AND HOW THIS |
| | AFFECTS EXITING, FBC 107. |
| | |
| | 14. A5.4, A5.4.1, CLARIFY DOOR CHANGES, FBC 107, IN |
| | PARTICULAR CODE RELATED CHANGES (PANIC DEVICES, |
| | CLOSERS, NON ACCESSIBLE HARDWARE, FIRE RATINGS, ETC.). |
| | |
| | 15. A8.2, DETAILS 12 AND 16, POSSIBLY OTHER LOCATIONS, |
| | STUCCO OVER SHEATHING IS TO HAVE A BOND BREAK TO |
| | PROPERLY RESIST WATER AND PROTECT THE VERTICAL |
| | SHEATHING. EITHER REVISE OR EXPLAIN RATIONALE. DUE TO |
| | THE CONFIGURATION OF THE DETAIL IT IS NOT CLEAR TO WHAT |
| | EXTENT THIS IS EXPOSED TO WEATHER, FBC 107. |
| | THIS AFFECTS OTHER DETAILS, FOR INSTANCE 9-A8.3, CHECK |
| | ALL. |
| | |
| | 16. DETAIL 9-S4.2 SHOWS WOOD TRUSSES, SEE FBC B 603.1 |
| | AND REVISE TO SPEC FRT OR CLARIFY. |
| | |
| | 17. SEE MECHANICAL COMMENTS REGARDING LOUVERS. PROVIDE |
| | SPEC SHEETS AND EVIDENCE OF COMPLIANCE WITH FBC B 1609, |
| | 603. ADDITIONAL INFORMATION MAY BE REQUIRED. |
| | |
| | |