| Plan Review Notes For Permit 17010547 |
| Permit Number |
17010547 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-01-20 06:18:30 | PLEASE NOTE THAT MULTIPLE UNITS AT THIS ADDRESS HAVE | | | BEEN UPGRADED RECENTLY TO 100AMP(EXISTING MULTIPLE | | | METER CANS). PLEASE PROVIDE A LOAD CALCULATION FOR THE | | | ENTIRE SERVICE TO VERIFY SERVICE CONDUCTORS ARE OF | | | SUFFICIENT SIZE TO CARRY ADDED LOADS. FBC 107.3.5 | | | PLEASE NOTE ON PLANS ASSOCIATED PLUMBING PERMIT # | | | ATTACHED TO THIS PROJECT WHICH INVOLVES A WATER | | | HEARTER. IS IT A INSTA HOT OR TANK? | | | ARE UNITS EQUIPED WITH SMOKE DETECTORS? CLARIFY | | | PROVIDE FLOOR PLAN INDICATING LOCATION OF RANGE AND | | | WATER HEATER. | | | | | | V. PEREZ | | | *6717 |
|