| Plan Review Notes For Permit 17010523 |
| Permit Number |
17010523 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-01-31 05:59:22 | 1) INDICATE THE OCCUPANT LOAD ON THE PLANS IN | | | COMPLIANCE WITH FBC-BUILDING TABLE 1004.1. | | | 2) WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS, | | | URINALS AND WATER CLOSETS SHALL COMPLY WITH 2014 | | | FBC-BUILDING SEC.1210.2.2. | | | 3) SHT. A1.4 - D6 - THE GRAB BARS SHALL BE MEASURED TO | | | THE TOP OF THE GRIPPING SURFACE. 2014 FBC-ACCESSIBILITY | | | SEC. 609.4. | | | 4) SHT.A1.4- DETAIL 6 - THE KNEE AND TOE CLEARANCE | | | SPACE UNDER THE ACCESSIBLE LAVATORY SHALL CCOMPLY WITH | | | 2014 FBC-ACCESSIBILITY SEC. 306. | | | 5) SUBMIT MANUFACT. SPECIFICATIONS FOR THE CONDENSATE | | | PUMP. WPB AMEND. TO FBC SEC. 107.2.1. | | | 6) SHT. P2.1 - KEYNOTE #2 NOTES THE CONDENSATE BRANCH | | | AS 1 1/2 INCH AND THE CONDENSATE PUMP LAYOUT SHOWS A 2 | | | INCH HEADER. CLARIFY. THE PLAN DOES NOT SHOW THE 2 INCH | | | HEADER. | | | 7) ALL COFFEE MAKERS & ICE MAKERS SHALL BE EQUIPPED | | | WITH BACKFFLOW PREVENTERS PER 2014 FBC-PLUMBING | | | SEC.608.3, 608.16.10. | | | 8) SHT.P5.1 - SHOWS A SINK ON A WET VENT WHICH IS NOT | | | PERMITTED PER 2014 FBC-PLUMBING SEC.912.1. AN | | | INDIVIDUAL VENT ON THE MOP SINK WWILL CORRECT THIS | | | ISSUE. | | | 9) SHT. P5.1 - WATER RISER - MEN'S RESTROOM #135 - IT | | | APPEARS THAT ONLY ONE WC-1 IS SHOWN ON THE WATER RISER. | | | CLARIFY. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|