| Plan Review Notes For Permit 17010488 |
| Permit Number |
17010488 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-03-27 17:15:18 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT # 17010488 | | | 3/27/17 | | | | | | 1) M1.01: PLEASE IDENTIFY ALL ROOMS AND SPACES ON THE | | | PLAN- SECTION M1601.1 FBC-14 RESIDENTIAL | | | | | | 2) M1.01: INDICATE HOW ACESS WILL BE PROVIDED FOR | | | MAINTENANCE AND REPLACEMENT OF THE AIR HANDLER- M1305.1 | | | | | | 3) M1.01: THE 6" FLEX DUCTS ARE UNDERSIZED FOR 150 CFMS | | | WHEN CHECKED WITH THE TRANE DUCTULATER USING 0.1 | | | FRICTION LOSS. | | | | | | 4) M1.01: PROVIDE STRUCTURAL DETAILS FOR INSTALLATION | | | OF THE CONDENSER PAD AND TIE DOWN OF THE CONDENSER- | | | M1305.1.4.1 | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|