| Plan Review Notes For Permit 17010488 |
| Permit Number |
17010488 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-02-08 13:55:15 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17010488 | | | 2/8/17 | | | | | | 1) PROVIDE AN AC EQUIPMENT SCHEDULE ON THE PLAN THAT | | | LISTS THE MAKES AND MODELS OF THE AIR HANDLER AND | | | CONDENSER, THE COOLING AND HEATING CAPACITIES OF THE | | | SYSTEM, AND THE EFFICIENCY RATING. | | | | | | 2) SUBMIT AN AHRI CERTIFICATE FOR THE AC SYSTEM. | | | | | | 3) PROVIDE DUCTWORK SPECIFICATIONS PER NOTE #5 ON SHEET | | | M1.01. | | | | | | 4) PROVIDE DIFFUSER AND RETURN GRILL SIZES AND THE | | | AIRFLOW CFMS AT EACH LOCATION. | | | | | | 5) PROVIDE AN EQUIPMENT SCHEUDLE FOR THE EXHAUST FAN. | | | | | | 6) PTROVIDE A CONDENSATE DISPOSAL PLAN. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|