| 2017-01-27 08:28:47 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17010483 |
| | ADD: 625 N. FLAGLER DR. #100 |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: 561-615-3903 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. JAN. 27/2017 |
| | ACTION: DENIED |
| | |
| | 1) THE PLANS DO NOT INDICATE THE ENERGIES DEVELOPED BY |
| | THE X-RAY UNIT. FOR UNITS THAT UTILIZING X-RAY ENERGIES |
| | OF 200 KEV AND ABOVE FOR DIAGNOSTIC OR THERAPEUTIC |
| | PURPOSES SHALL BE SUBMITTED TO THE DEPARTMENT OF HEALTH |
| | FOR REVIEW AND APPROVAL. |
| | |
| | 2) 2014 FBC-B 465.1.3. FOR X-RAY UNITS THAT UTILIZE |
| | ENERGIES OF 200 KEV AND ABOVE THE REQUIREMENTS OF FBC-B |
| | 465.1.3 (465.1.3.1- 465.5.1.3.3) MUST BE OBSERVED. FOR |
| | UNITS THAT USE LESS ENERGY THAN 200 KEV THEN THE |
| | MANUFACTURERS SPECIFICATIONS MUST BE MET. |
| | |
| | 3) SHEET A1.11 THE FLOOR PLAN INDICATES THE DOOR INTO |
| | THE X-RAY ROOM IS IDENTIFIED AS NUMBER 028. THE DOOR |
| | SCHEDULE LIST THE LOCK AS MANUFACTURER FALCON T511P6 |
| | DANE A LEVER LOCK. PLEASE REVIEW THE REQUIREMENTS FOUND |
| | IN SECTION: |
| | 465.6 OF THE 2014 FBC-B. DOORS, INTERLOCKS, AND WARNING |
| | SYSTEMS. |
| | |
| | 3.1) 465.6.1 A LICENSEE SHALL CONTROL ACCESS TO THE |
| | TELETHERAPY ROOM BY A DOOR AT EACH ENTRANCE. |
| | |
| | 3.2) 465.6.2 A LICENSEE SHALL EQUIP EACH ENTRANCE TO |
| | THE TELETHERAPY ROOM WITH AN ELECTRICAL INTERLOCK |
| | SYSTEM THAT SHALL: |
| | |
| | 3.3) 465.6.2.1. PREVENT THE OPERATOR FROM TURNING ON |
| | THE PRIMARY BEAM OF RADIATION UNLESS EACH TREATMENT |
| | ROOM ENTRANCE DOOR IS CLOSED; |
| | |
| | 465,6,2,2. TURN OFF THE BEAM OF RADIATION IMMEDIATELY |
| | WHEN AN ENTRANCE DOOR IS OPENED; AND |
| | |
| | 465.6.2.2. 3. PREVENT THE PRIMARY BEAM OF RADIATION |
| | FROM BEING TURNED ON FOLLOWING AN INTERLOCK |
| | INTERRUPTION UNTIL ALL TREATMENT ROOM ENTRANCE DOORS |
| | ARE CLOSED AND THE BEAM ON-OFF CONTROL IS |
| | RESET AT THE CONSOLE. |
| | |
| | 4) SHEET A4.21 THERE ARE VARIOUS ELEVATIONS OR VIEWS OF |
| | THE FRONT COUNTER WITH THE TRANSACTION COUNTER SURFACE |
| | AT AN ELEVATION OF 3 FT. 6 INCHES. 2014 |
| | FBC-ACCESSIBILITY CODE 904.3.3 CHECK WRITING SURFACES. |
| | WHERE PROVIDED, CHECK WRITING SURFACES SHALL COMPLY |
| | WITH 902.3. |
| | 2014 FBC-ACCESS. CODE 902.3 HEIGHT. THE TOPS OF DINING |
| | SURFACES AND WORK SURFACES SHALL BE 28 INCHES (710 MM) |
| | MINIMUM AND 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. |
| | |
| | 4) SHEET A4.22 SHOW WALL TILE INSTALLED IN ALL WET |
| | AREAS. SHEET A0.15 IN ALL WET AREAS THE SCHEDULE |
| | INDICATES A TILE FOR THE FINISH WALL AND WALL MATERIAL |
| | TO BE GYPSUM. PLEASE REVIEW SECTIONS 2509.2 BASE FOR |
| | TILE & 2509.3 LIMITATIONS OF WATER RESISTANT GYPSUM. |
| | 2014 FBC-B. |
| | |
| | 5) SHEET A4.22 DETAIL # 5 SHOWS THE WATER CLOSET TILE |
| | BARS INSTALLED AND MEASURED FROM CENTERLINE. |
| | PLEASE REVIEW THE 2014 FBC-ACCESSIBILITY CODE SECTION |
| | 609.4 POSITION OF GRAB BAR. GRAB BARS SHALL BE |
| | INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM |
| | AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED |
| | TO THE TOP OF THE GRIPPING SURFACE. |
| | |
| | 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. |
| | WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |