| 2017-01-27 12:22:38 | 1) TOILET ROOMS #204 AND #205 SHALL HAVE HANDICAPPED |
| | ACCESSIBLE TOILET COMPARTMENTS LOCATED WITHIN THE |
| | RESTROOMS PER THE 2014 FBC- ACCESSIBILITY SEC.213.3.1. |
| | THE TOILET COMPARTMENT DIMENSIONS SHALL COMPLY WITH |
| | 2014 FBC - ACCESS. SECS. 305, 604. |
| | 2) A LAVATORY SHALL BE LOCATED WITHIN EACH REQUIRED |
| | TOILET COMPARTMENT PER THE 2014 FBC SEC.604.8.1.6. |
| | 3) SHOW THE CLEAR INSIDE DIMENSIONS OF ALL TOILET |
| | ROOMS. ACCESSIBLE TOILET ROOMS SHALL COMPLY WITH 2014 |
| | FBC-ACCESSIBILITY SECS. 604.3 FOR WATER CLOSETS AND |
| | SEC.606.2 FOR LAVATORIES. |
| | 4) A 30 INCH WIDE BY 48 INCH LONG CLEAR FLOOR SPACE |
| | CENTERED ON THE FIXTURE IS REQUIRED FOR THE BREAK ROOM |
| | SINK. COMPLY WITH FBC-ACCESS. SEC.606.2. |
| | 5) THE ACCESSIBLE DRINKING FOUNTAIN LOCATED IN CORRIDOR |
| | # 206 SHALL COMPLY WITH 2014 FBC- ACCESS. SEC.307.2 FOR |
| | PROTRUSION LIMITS. |
| | 6) SHT. A4.22 - REFERENCED IS MADE TO THE 2010 FBCA. |
| | THE CODEE IN EFFECT IS THE 2014 FBC. |
| | 7) SHT. A4.23 - THE HEIGHT OF THE GRAB BARS SHALL BE |
| | MEASURED TO THE TOP OF THE GRIPPING SURFACE PER 2014 |
| | FBC SEC.609.4. |
| | 8) THE MAXXIMUM REACH RANGE HEIGHT FOR THE PAPER TOWEL |
| | DISPENSER SHALL COMPLY WITH 2014 FBC - ACCESS. SEC.308. |
| | 9) SHOW THE CAPACITY OF THE EXPANSION TANK ON THE WATER |
| | HEATER. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 10) SHT. P5.1 - SIZE ALL VENTS ON THE SANITARY RISER. |
| | COMPLY WITH 2014 FBC-PLUMBING SEC.906.1. |
| | 11) THE VENT FOR THE TWO MOST UPSTREAM WATER CLOSETS ON |
| | THE SANITARY RISER ( TOILET ROOMS 204 & 205 ) SHALL BE |
| | TAKEN OFF BETWEEN THE WATER CLOSETS . 2014 FBC-PLUMBING |
| | SEC.901.2, 905.3. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |