| Plan Review Notes For Permit 17010448 |
| Permit Number |
17010448 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-01-20 07:19:16 | PROVIDE A PANEL SCHEDULE AND SHOW WHICH CIRCUIT #'S ARE | | | FEEDING AREA OF CUBICLES. | | | | | | CLARIFY THE AMOUNT OF SPACES TO BE FED AND RECEPTACLES. | | | PER NEC 605.8 (B,C,D) APPLY. SHOW TO COMPLY | | | | | | IS LOW VOLTAGE DEVICES FOR DATA AND PHONE PART OF | | | SCOPE? | | | | | | V. PEREZ | | | *6717 |
|