| Plan Review Notes For Permit 17010407 |
| Permit Number |
17010407 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-01-25 18:18:48 | REVISION 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1] PROVIDE ELECTRICAL PLANS TO INCLUDE RISER DIAGRAM | | | WITH CONDUIT & WIRE SIZES, GROUNDING DETAIL, COMPLETE | | | LOAD CALCULATIONS, & PANEL SCHEDULES. FBC-107.3.5.3 | | | | | | 2] PLANS MUST BE SIGN AND SEALED BY DESIGN PROFFESIONAL | | | AND SUBMITTED IN 2 COPIES. FBC-107 | | | | | | 3] SHOW 2 20 AMP SMALL APPLIANCE CIRCUITS & SHOW GFCI | | | RECEPTACLE OUTLET SPACING IN KITCHEN. FBC-R SECTIONS | | | E3901.3 & E3902.6 | | | | | | 4] SHOW A 20 AMP CIRCUIT & SHOW GFCI RECEPTACLE OUTLET | | | WITHIN 3' OF BATHROOM SINK. FBC-R SECTIONS E3901.6 & | | | E3902.1 | | | | | | 5] SMOKE ALARMS REQUIRED PER FBC-R SECTIONS 314 & 315. | | | | | | 6] TAMPER RESISITANT RECEPTACLES REQUIRED PER FBC-R | | | SECTION E4002.14. | | | | | | |
|