| 2017-01-27 11:08:08 | 1ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL, EXISTING |
| | BUILDING CODE |
| | |
| | THIS IS A REVIEW FOR RE-ISSUANCE OF EXPIRED PERMIT |
| | 05110768. THE PROJECT WAS COMPLETED BUT ALL REQUIRED |
| | INSPECTIONS WERE NOT APPROVED. SEE R REVIEW FOR ROOF |
| | COVERING REQUIREMENTS AND ELECTRIC REVIEW FOR |
| | ELECTRICAL REQUIREMNTS. THERE IS NO RECORD OF A |
| | REQUIRED INSULATION INSPECTION. YOU MUST SATISFY THE |
| | INSPECTOR BY CERTIFICATION TEST OR EXPOSING THE WORK |
| | SUFFICIENTLY TO VERIFY THE INSTALLATION. REF. FBC 110. |
| | PLEASE NOTE THE PLAN SHOW AN EXTERIOR HARDIPLANK |
| | SIDING, HOWEVER UNDER PERMIT 07070773, A CHANGE WAS |
| | MADE TO STUCCO AND THAT PERMIT RECEIVED THE REQUIRED |
| | INSPECTIONS. THIS IS NOTED ON THE PLAN FOR RECORD |
| | PURPOSES. PLEASE NOTE THE OWNER INDICATES THE STORM |
| | PANELS ON FILE FROM THE ORIGINAL PERMIT DOCUMENTS ARE |
| | NOT PROVIDED ON SITE. ACCORDINGLY, A LICENSED |
| | CONTRACTOR MUST BE ENGAGED BY THE OWNER AND A SEPARATE |
| | PERMIT MUST BE OBTAINED TO INSTALL NEW CODE COMPLIANT |
| | SHUTTERS FOR THE NEW WINDOW OPENINGS ON THE EXTERIOR |
| | WALLS SHOWN ON THE RECORD SET OF PLANS 05110768. REF |
| | FBC R301.2.1.2 PROTECTION OF OPENINGS AND FS 489.103. A |
| | FINAL INSPECTION WAS NEVER SCHEDULED AND IS REQUIRED |
| | HOWEVER, IT MAY NOT BE SCHEDULED UNTIL SUCH TIME AS THE |
| | HURRICANE PANEL, ELECTRICAL AND ROOFING PERRMITS ARE |
| | COMPLETED AND HAVE RECEIVED FINAL APPROVED INSPECTIONS. |
| | . |
| | |
| | STEVEN KENNEDY, CBO |
| | CHIEF PLANS EXAMINER |
| | (561) 805-6710 |
| | [email protected] |
| | |