| Plan Review Notes For Permit 17010390 |
| Permit Number |
17010390 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-01-18 05:47:50 | AN AIR ADMITTANCE CANNOT BE USED IN A PLUMBING SYSTEM | | | WITHOUT A MINIMUM OF ONE STACK VENT OR VENT STACK | | | EXTENDED TO THE OUTDOORS TO THE OPEN AIR PER 2014 | | | FBC-PLUMBING SEC. 918.7. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|