| 2017-05-31 15:13:43 | 1) SHT.A2.613 & SHT. RP2.0 SHOW TWO WATER SUPPLIED |
| | CHILLERS IN THE EQUIPMENT PIT. THE WATER SUPPLY TO THE |
| | CHILLERS SHALL BE EQUIPPED WITH A BACKFLOW PREVENTER |
| | PER THE 2014 FBC- PLUMBING SEC. 608.3. |
| | 2) SUBMIT A POOL PIPING PLAN VIEW THAT CLEARLY REFLECTS |
| | THE LOCATION OF THE MAIN DRAINS, SKIMMERS AND RETURNS |
| | FOR EACH PLUNGE POOL. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 3) PROVIDE THE TURNOVER RATE FOR EACH SPA ON THE PLANS. |
| | THE TURNOVER RATE FOR EACH SPA SHALL COMPLY WITH 2014 |
| | FBC-BUILDING SEC.454.1.8.8. |
| | 4) AUTOMATED OXIDATION REDUCTION POTENTIAL (ORP) AND PH |
| | CONTROLLERS WITH SENSING PROBES SHALL BE INSTALLED ON |
| | SPA POOLS TO ASSIST IN MAINTAINING PROPER DISINFECTION |
| | AND PH LEVELS. 2014 FBC-BUILDING SEC.454.1.8.12. |
| | 5) THERAPY OR JET PUMPS SHALL TAKE SUCTION FROM THE |
| | COLLECTOR TANK. 2014 FBC-BUILDING SEC. 454.1.8.6.2, |
| | 6) PROVIDE DETAILS FOR MAKEUP WATER. THE MAKEUP WATER |
| | LINE SHALL BE PROTECTED AGAINST BACKFLOW PER 2014 |
| | FBC-PLUMBING SEC. 608.1. |
| | 7) A FIXED THERMOMETER SHALL BE MOUNTED IN THE POOL |
| | RECIRCULATION DOWNSTREAM FROM THE HEATER |
| | OUTLET.THERMOMETERS MOUNTED ON HEATER OUTLETS DO NOT |
| | MEET THIS REQUIREMENT. 2014 FBC-BUILDING |
| | SECS.454.1.6.5.14, 454.1.8.1. |
| | 8) THE FLOW VELOCITY IN SUCTION PIPING SHALL NOT EXCEED |
| | 6 FT. PER SECOND. THE MAIN DRAIN SPECS SHOW 6.42 FPS. |
| | CLARIFY. 2014 FBC SEC. 454.1.6.5.8. |
| | 9) PAGE 3 - UTILITIES SECTION OF THE HYDROWORX DESIGN |
| | GUIDE SPECIFIES THAT A MINIMUM 2 INCH WATER SUPPLY LINE |
| | WITH ANTI-SIPHON DEVICE BE CONNECTED TO THE |
| | RECIRCULATION RETURN LINE, A 3/4" DIAMETER HOSE BIBB |
| | WITH ANT-SIPHON IN THE POOLROOM AND A 1- 1/2 INCH OR 2 |
| | INCH DIAMETER BUILDING LOOP LINE TO AND FROM THE WATER |
| | COOLED CHILLER. SUPPLY THIS INFORMATION/DETAIL FOR |
| | REVIEW. SUBMIT PLUMBING SCHEMATIC FROM HYDROWORX. |
| | 10) INDICATE WHAT MEANS IS PROVIDED FOR DRAINING THE |
| | SPAS. |
| | 11) PAGE 7 OF THE HYDROWORX DESIGN GUIDE RECOMMENDS |
| | INSULATION OF THE CHILLED WATER. PROVIDE DETAIL ON |
| | THICKNES OF INSULATION. |
| | |