| Plan Review Notes For Permit 17010377 |
| Permit Number |
17010377 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-01-14 08:53:53 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA RES BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 | | | COMMENTS: | | | | | | 1. SHOW AN INTERSYSTEM BONDING TERMINAL AT THE SERVICE | | | PER FBC RES E3609.3 | | | 2. PROVIDE A ONE-LINE RISER DIAGRAM FOR THE SERVICE. | | | FBC 107.3.5 | | | 3. MAIN CB TO BE LOCATED OUTSIDE THE DWELLING. | | | 4. SHOW BONDING AND GROUNDING REQUIREMENTS. | | | 5. CLARIFY IF THE PANEL SHOWN IS IN A CLOSET OR HALL. | | | PANEL CANNOT BE LOCATED IN CLOSET PER FBC RES E3705.7 | | | 6. SHOW SMOKE DETECTORS ON DRAWINGS CLARIFY IF EXISTING | | | OR NEW. FBC RES 314. | | | 7. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY | | | QUESTIONS OR CONCERNS. | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | | | | |
|