2017-01-14 08:53:53INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA RES BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. SHOW AN INTERSYSTEM BONDING TERMINAL AT THE SERVICE
 PER FBC RES E3609.3
 2. PROVIDE A ONE-LINE RISER DIAGRAM FOR THE SERVICE.
 FBC 107.3.5
 3. MAIN CB TO BE LOCATED OUTSIDE THE DWELLING.
 4. SHOW BONDING AND GROUNDING REQUIREMENTS.
 5. CLARIFY IF THE PANEL SHOWN IS IN A CLOSET OR HALL.
 PANEL CANNOT BE LOCATED IN CLOSET PER FBC RES E3705.7
 6. SHOW SMOKE DETECTORS ON DRAWINGS CLARIFY IF EXISTING
 OR NEW. FBC RES 314.
 7. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS OR CONCERNS.
  