| 2017-01-19 13:01:13 | RESIDENTIAL (R3) MECHANICAL REVISION COMMENTS. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- THERE IS AN ENGINEER OF RECORD WHO DESIGNED THE | | | MECHANICAL PLANS. PLANS NEED TO BE SIGNED AND SEALED BY | | | THE ENGINEER OF RECORD SHOWN ON THE BOTTOM RIGHT OF | | | PLANS. CHAPTER 471 FLORIDA STATUTE. | | | | | | 2- EQUIPMENT MANUFACTURER WAS CHANGED. THE SEER FOR NEW | | | EQUIPMENT IS 16 SEER. ORIGINAL PLANS AND ENERGY | | | CALCULATIONS WERE APPROVED WITH 19.50 SEER. NEED TO | | | PROVIDE EQUIPMENT WITH 19.50 SEER EFFICIENCY OR | | | ENGINEER OF RECORD WHO PERFORMED THE ENERGY | | | CALCULATIONS NEED TO REVISE THE ENERGY CALCULATIONS | | | ACCORDINGLY. SEC. R103.2 FBC-ENERGY CONSERVATION, 5TH | | | EDITION (2014). | | | | | | 3- LIVING ROOM NEEDS TO COMPLY WITH THE BALANCED RETURN | | | AIR SEC. M1602.4 FBC-RESIDENTIAL, 5TH EDITION (2014). | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|