| 2017-10-04 07:14:24 | 10/4/17 3RD PLUMBING REVIEW*DENIED* |
| | |
| | FURTHER PLAN REVIEW COULD RESULT IN A 4X PLAN REVIEW |
| | FEE PER F.S.553.7.9 (B) (2) |
| | |
| | ONLY 1 OF THE 7 COMMENTS HAVE BEEN ADDRESS FROM 2ND |
| | PLAN REVIEW REGRADING THE CORRECT SIZING TABLE. PLEASE |
| | REVIEW PLAN REVIEW 2ND COMMENTS AND CALL REVIEWER |
| | BEFORE SUBMITTING CORRECTIONS |
| | |
| | 1) THE GAS DRYER IN THE GARAGE SHALL BE PROTECTED FROM |
| | PHYSICAL DAMAGE PER 2014 FBC-FUEL GAS SEC. 305.5. |
| | 2) THE INSTALLATION OF THE DRYER SHALL COMPLY WITH THE |
| | FUEL GAS CODE SEC. 305.3. |
| | 3) SUBMIT MANUF. SPECIFICATIONS FOR THE POOL HEATER. |
| | THE POOL HEATER SHALL BE LISTED AND LABELED PER 2014 |
| | FBC SEC. 301.3. |
| | 4) THE POOL HEATER SHALL COMPLY WITH 2014 FBC-ENERGY |
| | SEC. R403.9.1.1. |
| | 5) THE INSTALLATION SHEET I PRINTED FROM THE DESIGN |
| | MANUAL SHOWS A REQUIRED DISTANCE OF 4 FEET FROM |
| | OPERABLE DOORS OR WINDOWS AND YOU HAVE STATED ON THE |
| | PLANS A DISTANCE OF ONE FOOT IS REQUIRED. CLARIFY. |
| | REFER TO THE MANUF. SHEET. I PLACED IN YOUR PLANS. |
| | 6) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE DRYER. |
| | YOU HAVE SUPPLIED A NUMBER OF 2496 CUBIC FEET BUT ALSO |
| | REFERENCED SEC.614.5 OF THE FUEL GAS CODE WHICH |
| | REQUIRES INSTALLATIONS EXHAUSTING MMORE THAN 200 CFM'S |
| | TO BE PROVIDED WITH MAKEUP AIR. THIS IS CONFUSING AS TO |
| | HOW YOU ARE COMPLYING. CLARIFY HOW YOU ARE COMPLYING |
| | WITH THE GAS CODE FOR COMBUSTION AIR. |
| | |
| | |
| | NOTE: IT MAY BE BENEFICIAL FOR THE CONTRACTOR TO CALL |
| | AND SET UP AN APPOINTMENT TO GO OVER THESE COMMENTS. |
| | |
| | TIM HUNT |
| | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER |
| | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | 561-805-6695 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |