Plan Review Notes
Plan Review Notes For Permit 17010279
Permit Number 17010279
Review Stop G
Sequence Number 3
Notes
Date Text
2017-10-04 07:14:2410/4/17 3RD PLUMBING REVIEW*DENIED*
  
 FURTHER PLAN REVIEW COULD RESULT IN A 4X PLAN REVIEW
 FEE PER F.S.553.7.9 (B) (2)
  
 ONLY 1 OF THE 7 COMMENTS HAVE BEEN ADDRESS FROM 2ND
 PLAN REVIEW REGRADING THE CORRECT SIZING TABLE. PLEASE
 REVIEW PLAN REVIEW 2ND COMMENTS AND CALL REVIEWER
 BEFORE SUBMITTING CORRECTIONS
  
 1) THE GAS DRYER IN THE GARAGE SHALL BE PROTECTED FROM
 PHYSICAL DAMAGE PER 2014 FBC-FUEL GAS SEC. 305.5.
 2) THE INSTALLATION OF THE DRYER SHALL COMPLY WITH THE
 FUEL GAS CODE SEC. 305.3.
 3) SUBMIT MANUF. SPECIFICATIONS FOR THE POOL HEATER.
 THE POOL HEATER SHALL BE LISTED AND LABELED PER 2014
 FBC SEC. 301.3.
 4) THE POOL HEATER SHALL COMPLY WITH 2014 FBC-ENERGY
 SEC. R403.9.1.1.
 5) THE INSTALLATION SHEET I PRINTED FROM THE DESIGN
 MANUAL SHOWS A REQUIRED DISTANCE OF 4 FEET FROM
 OPERABLE DOORS OR WINDOWS AND YOU HAVE STATED ON THE
 PLANS A DISTANCE OF ONE FOOT IS REQUIRED. CLARIFY.
 REFER TO THE MANUF. SHEET. I PLACED IN YOUR PLANS.
 6) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE DRYER.
 YOU HAVE SUPPLIED A NUMBER OF 2496 CUBIC FEET BUT ALSO
 REFERENCED SEC.614.5 OF THE FUEL GAS CODE WHICH
 REQUIRES INSTALLATIONS EXHAUSTING MMORE THAN 200 CFM'S
 TO BE PROVIDED WITH MAKEUP AIR. THIS IS CONFUSING AS TO
 HOW YOU ARE COMPLYING. CLARIFY HOW YOU ARE COMPLYING
 WITH THE GAS CODE FOR COMBUSTION AIR.
  
  
 NOTE: IT MAY BE BENEFICIAL FOR THE CONTRACTOR TO CALL
 AND SET UP AN APPOINTMENT TO GO OVER THESE COMMENTS.
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  
  
  
  
  
  