| Date |
Text |
| 2017-04-14 06:05:57 | 1) THE GAS DRYER IN THE GARAGE SHALL BE PROTECTED FROM |
| | PHYSICAL DAMAGE PER 2014 FBC-FUEL GAS SEC. 305.5. |
| | 2) THE INSTALLATION OF THE DRYER SHALL COMPLY WITH THE |
| | FUEL GAS CODE SEC. 305.3. |
| | 3) THE PLAN NOTES THAT PE PIPE WILL BE USED TO SUPPLY |
| | GAS TO THE POOL HEATER BUT THE SIZING TABLE THAT WAS |
| | SUBMITTED IS FOR COPPER TUBING. SUBMIT 2 COPIES OF THE |
| | SIZING TABLE FOR PE PIPE THAT IS BEING USED. |
| | 4) SUBMIT MANUF. SPECIFICATIONS FOR THE POOL HEATER. |
| | THE POOL HEATER SHALL BE LISTED AND LABELED PER 2014 |
| | FBC SEC. 301.3. |
| | 5) THE POOL HEATER SHALL COMPLY WITH 2014 FBC-ENERGY |
| | SEC. R403.9.1.1. |
| | 6) THE INSTALLATION SHEET I PRINTED FROM THE DESIGN |
| | MANUAL SHOWS A REQUIRED DISTANCE OF 4 FEET FROM |
| | OPERABLE DOORS OR WINDOWS AND YOU HAVE STATED ON THE |
| | PLANS A DISTANCE OF ONE FOOT IS REQUIRED. CLARIFY. |
| | REFER TO THE MANUF. SHEET. I PLACED IN YOUR PLANS. |
| | 7) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE DRYER. |
| | YOU HAVE SUPPLIED A NUMBER OF 2496 CUBIC FEET BUT ALSO |
| | REFERENCED SEC.614.5 OF THE FUEL GAS CODE WHICH |
| | REQUIRES INSTALLATIONS EXHAUSTING MMORE THAN 200 CFM'S |
| | TO BE PROVIDED WITH MAKEUP AIR. THIS IS CONFUSING AS TO |
| | HOW YOU ARE COMPLYING. CLARIFY HOW YOU ARE COMPLYING |
| | WITH THE GAS CODE FOR COMBUSTION AIR. |
| | |
| | |
| | NOTE: IT MAY BE BENEFICIAL FOR THE CONTRACTOR TO CALL |
| | AND SET UP AN APPOINTMENT TO GO OVER THESE COMMENTS. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |