| 2017-02-08 15:13:00 | ****CORRECTIONS**** |
| | REVISED 2/13/17 |
| | REVISED 2/14/17 |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | 1. THE ASSEMBLY SELECTED REFERS TO GENERAL LIMITATION |
| | #9. SEE GENERAL LIMITATIONS ON PAGE 16. #7 WAS CIRCLED, |
| | BUT IS NOT APPLICABLE. #9 DOES NOT ALLOW ENHANCED |
| | FASTENING. |
| | |
| | PLEASE SELECT A DIFFERENT ASSEMBLY AND REVISE |
| | ENGINEERING. AS DISCUSSED, THIS MAY BE SENT VIA EMAIL |
| | FOR PRELIMINARY REVIEW WITH ORIGINAL REQUIRED AT TIME |
| | OF PICKUP. |
| | |
| | (NOTE - CONTRACTOR AND ENGINEER ELECTED NOT TO PROVIDE |
| | VIA EMAIL) |
| | |
| | 2. REGARDING THE CALCULATIONS, FBC R 301: |
| | |
| | FBC 5TH EDITION RESIDENTIAL FIGURE 301.2(7), ZONE 3 TO |
| | EQUAL 4' IN ALL CASES. |
| | |
| | CLARIFY SHEET WIDTH OF 60. SEE THE NOA PROVIDED, THE |
| | BASE SHEETS FOR THE SELECTED ASSEMBLY ARE ALL 36" IN |
| | WIDTH. |
| | |
| | PROVIDE THE PAGES OF THE NOA WHICH APPLY TO ALL |
| | ASSEMBLIES; THIS SHOULD INCLUDE THE FIRST PAGES WHICH |
| | PROVIDE PRODUCT DESCRIPTIONS. |
| | |
| | CLARIFY 14" ROW SPACING; THE ATTACHMENT REQUIREMENTS |
| | SPECIFY FOUR ROWS 14" APART, BUT THE SHEET IS ONLY 36". |
| | ARE YOU PROPOSING AN ALTERNATE PRODUCT? |
| | |
| | CLARIFY SPECIFICATION; 4 ROWS PROPOSED; CONFIRM THAT |
| | THIS IS FOUR ROWS TOTAL (ONE IN THE 4" LAP AND THREE IN |
| | THE FIELD), OR REVISE TO CLARIFY. |
| | |
| | ZONE 2 SPECIFIES 4.8" OC W/12" SIDELAP SPACING - |
| | CLARIFY HOW IT IS POSSIBLE FOR THE LAP TO BE 12", A |
| | DRAWING MAY BE REQUIRED. 4" OR LESS IS TYPICAL. THE |
| | SPECIFICATION OF A 12" LAP DOES NOT FOLLOW THE RAS117 |
| | REQUIREMENTS, REVISE OR CLARIFY. |
| | |
| | ZONE 2 SPECIFIES 4.8"; SEE RAS 117 10.4.5, ALL |
| | FRACTIONS TO BE ROUNDED DOWN TO THE NEXT WHOLE NUMBER. |
| | |
| | ZONE 3 SPECIFIES 3.2" SPACING; SEE RAS 117 10.4.5, ALL |
| | FRACTIONS TO BE ROUNDED DOWN TO THE NEXT WHOLE NUMBER. |
| | |
| | ZONE 3 SPECIFIES 3.2" SPACING; SEE RAS 117 8.1, THE |
| | MINIMUM FASTENER SEPARATION SHALL NOT BE LESS THAN 4 IN |
| | OC. |
| | |
| | THE CALCULATIONS DO NOT APPEAR CORRECT. HOWEVER, THE |
| | SPECIFICATION IS WHAT WILL DETERMINE WHETHER OR NOT THE |
| | CALCULATIONS WILL BE ACCEPTED (PASS PLAN REVIEW). A |
| | COMPLIANT SPECIFICATION WILL RESULT IN PERMIT ISSUANCE, |
| | EVEN IF THE CALCULATIONS ARE NOT CORRECT (NOT IN |
| | ACCORDANCE WITH RAS 117). |
| | |
| | NEW COMMENT 2/14/17 |
| | |
| | KATI FROM JIJ CONSTRUCTION MARKED ALL FOUR PRODUCT |
| | APPROVALS "VOID" (TWO SHINGLE, TWO FLAT). NO ADDITIONAL |
| | PRODUCT APPROVALS WERE SUBMITTED. WHEN RESUBMITTING, |
| | PROVIDE TWO COMPLETE SETS OF PRODUCT APPROVALS TO |
| | REPLACE THE VOIDED PRODUCT APPROVALS |
| | |
| | |
| | |