| Plan Review Notes For Permit 17010250 |
| Permit Number |
17010250 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-01-09 18:12:49 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. TWO COMPLETE SETS OF PERMIT DOCUMENTS REQUIRED FOR | | | PERMIT ISSUANCE, FBC 107. ONLY ONE SET OF PRODUCT | | | APPROVALS WAS SUBMITTED. | | | | | | 2. CLARIFY PROPOSED INSTALLATION. ASSEMBLY C WAS | | | CIRCLED ON TABLE A. IS ASSEMBLY C PROPOSED FOR ZONES 1, | | | 2, AND 3? NOTE THAT, PER THE TABLE, MINIMUM DESIGN | | | REQUIRES ASSEMBLY A IN ZONES 1 AND 2, ASSEMBLY B IS | | | REQUIRED FOR ZONE 3. IT IS ACCEPTABLE TO EXCEED MINIMUM | | | CODE COMPLIANCE. PLEASE CONFIRM THAT ASSEMBLY A (WHICH | | | REQUIRES SEALANT) IS PROPOSED THROUGHOUT THE ENTIRE | | | ROOF. IF THIS IS NOT WHAT IS PROPOSED, PLEASE "VOID" | | | THIS PAGE, PROVIDE PRODUCT APPROVAL INDICATING THE | | | PROPOSED INSTALLATION. | | | | | | IF ASSEMBLY C IS SELECTED, THIS WILL BE ENFORCED AT | | | INSPECTION. A REVISION THROUGH PLAN REVIEW WOULD BE | | | REQUIRED TO USE AN ALTERNATE INSTALLATION METHOD. |
|