| Notes |
| Date |
Text |
| 2017-02-07 13:07:12 | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | ELECTRICAL REVIEW COMMENT. | | | | | | FEEDER TO PANEL C IS UNDER SIZED BASED ON THE | | | OVERCURRENT PROTECTION PROVIDED. NEC 240.4 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6654 | | | 561-373-3701 | | | [email protected] | | | | | | |
|