| 2017-01-27 18:54:15 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) SUBMIT TWO SETS OF A RECENT SURVEY. FBC 107.2.1 |
| | |
| | 2) A SEPARATE PERMIT, APPLICATION AND REVIEW IS |
| | REQUIRED FOR A FENCE PERMIT. |
| | |
| | 3) SUBMIT TWO SETS OF ENERGY CODE COMPLIANCE FORMS AS |
| | REQUIRED BY FBC ENERGY CONSERVATION SECTION R101.5.1.1. |
| | |
| | 4) SHOW COMPLIANCE WITH FBC-R 806.2 MINIMUM VENT AREA. |
| | THE MINIMUM NET FREE VENTILATING AREA SHALL BE 1/150 OF |
| | THE AREA OF THE VENTED SPACE. |
| | |
| | 5) SHOW COMPLIANCE WITH FBC-R408.2 OPENINGS FOR |
| | UNDER-FLOOR VENTILATION. THE MINIMUM NET AREA OF |
| | VENTILATION OPENINGS SHALL NOT BE LESS THAN 1 SQUARE |
| | FOOT FOR EACH 150 SQUARE FEET OF UNDER-FLOOR AREA. ONE |
| | VENTILATION OPENING SHALL BE WITHIN 3 FEET (915 MM) OF |
| | EACH CORNER OF THE BUILDING. |
| | |
| | 6) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| | FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC |
| | 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE |
| | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER |
| | OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH |
| | FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS |
| | AND MAXIMUM DESIGN PRESSURES FOR THE STRUCTURAL |
| | MULLIONS. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |