| Date |
Text |
| 2017-02-21 16:47:58 | 3RD REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17010175 |
| | 2/21/17 |
| | |
| | 1) AS PREVIOUSLY NOTED IN THE SECOND REVIEW, TWO COPIES |
| | OF THE PLANS AND SUBMITTALS ARE REQUIRED PER SECTION |
| | 107.2.1 WPB AMENDMENTS. MISSING ARE DUPLICATE COPIES OF |
| | THE MASTERBILT POWER PLAN DRAWING #5687- REV- 002, AND |
| | THE SUBMITTAL FOR THE GLASS DOOR MERCHANDISERS. |
| | |
| | 2) 2ND REQUEST FOR PLANS TO BE BOUND NEATLY TOGETHER IN |
| | TWO SEPARATE SETS. |
| | |
| | 2ND REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17010175 |
| | 2/13/17 |
| | |
| | 1) THE CITY OF WEST PALM BEACH CONSTRUCTION SERVICES |
| | DEPARTMENT REQUIRES THAT ALL PLANS AND SPECIFICATIONS |
| | FOR PERMITING PURPOSES BE SUBMITTED IN DUPLICATE. THE |
| | CURRENT SUBMITTAL IS MISSING DUPLICATE COPIES OF THE |
| | MASTERBILT PLANS, THE ROOF STAND PLANS, AND THE FREEZER |
| | DOOR DETAILS. A) PLEASE SEPARATE THE PLANS AND |
| | SUBMITTALS INTO TWO DUPLICATE SETS AND PERMANENTLY BIND |
| | THE |
| | |
| | INDIVIDUAL PAGES OF THE MAIN PLAN FROM CTA, AND THE |
| | MASTERBILT PLAN. |
| | |
| | 2) THE STRUCTURAL ENGINEERING PLAN FOR INSTALLATION OF |
| | THE ROOFTOP MASTERBILT UNIT SHALL BEAR THE SIGNATURE |
| | AND SEAL OF A FL. LICENSED PE.- SEE SECTION |
| | 61G15-23.002 FLORIDA ADMINISTRATIVE CODE AND FL. |
| | STATUTES 471.003. |
| | |
| | 3) THE ENGINEER OF RECORD MUST CIRCLE, HIGHLIGHT, OR |
| | OTHWERWISE MARK ALL APPLICABLE DETAILS, ASSEMBLIES, AND |
| | DESIGN PRESSURES ETC. ON THE PRECISION ROOF STAND |
| | PRODUCT APPROVAL. AS NOTED IN COMMENT #1 TWO COMPLETE |
| | COPIES ARE REQUIRED. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |