| Plan Review Notes For Permit 17010175 |
| Permit Number |
17010175 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-02-13 11:24:53 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #17010175 | | | 2/13/17 | | | | | | 1) THE CITY OF WEST PALM BEACH CONSTRUCTION SERVICES | | | DEPARTMENT REQUIRES THAT ALL PLANS AND SPECIFICATIONS | | | FOR PERMITING PURPOSES BE SUBMITTED IN DUPLICATE. THE | | | CURRENT SUBMITTAL IS MISSING DUPLICATE COPIES OF THE | | | MASTERBILT PLANS, THE ROOF STAND PLANS, AND THE FREEZER | | | DOOR DETAILS. A) PLEASE SEPARATE THE PLANS AND | | | SUBMITTALS INTO TWO DUPLICATE SETS AND PERMANENTLY BIND | | | THE | | | | | | INDIVIDUAL PAGES OF THE MAIN PLAN FROM CTA, AND THE | | | MASTERBILT PLAN. | | | | | | 2) THE STRUCTURAL ENGINEERING PLAN FOR INSTALLATION OF | | | THE ROOFTOP MASTERBILT UNIT SHALL BEAR THE SIGNATURE | | | AND SEAL OF A FL. LICENSED PE.- SEE SECTION | | | 61G15-23.002 FLORIDA ADMINISTRATIVE CODE AND FL. | | | STATUTES 471.003. | | | | | | 3) THE ENGINEER OF RECORD MUST CIRCLE, HIGHLIGHT, OR | | | OTHWERWISE MARK ALL APPLICABLE DETAILS, ASSEMBLIES, AND | | | DESIGN PRESSURES ETC. ON THE PRECISION ROOF STAND | | | PRODUCT APPROVAL. AS NOTED IN COMMENT #1 TWO COMPLETE | | | COPIES ARE REQUIRED. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|