| 2017-02-22 08:59:30 | BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 17010175 |
| | W. P. B. PERMIT: 15100991/ WAWA CONVENIENCE STORE |
| | ADD: 1520 BELVEDERE RD. |
| | CONT: COMPREHENSIVE ENERGY SERVICES |
| | TEL: 407-682-1313 |
| | E-MAIL: [email protected] / |
| | [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2ND REVIEW |
| | DATE: WED. FEB. 22/ 2017 |
| | ACTION: DENIED |
| | |
| | NOTICE!!!!!! **** 4X FEE NOTICE!!!!! FLORIDA STATUTE |
| | 553.80(2)(B)**** |
| | |
| | |
| | |
| | WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | |
| | |
| | 1) 2ND REQUEST! SUBMIT PLANS COLLATED INTO (2) PERMIT |
| | READY SETS OF PLANS. |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION THE BUILDING OFFICIAL MAY ESTABLISH |
| | THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS |
| | AND SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO |
| | ITS RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE |
| | SUCH THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, |
| | OR OTHER ITEMS RELATED TO RECORDS MANAGEMENT. |
| | ELECTRONIC MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE |
| | REQUIREMENTS OF FLORIDA STATUTES. |
| | 107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF |
| | CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL |
| | INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL |
| | BE SUBMITTED IN TWO OR MORE SETS WITH EACH |
| | PERMIT APPLICATION. |
| | |
| | 2) DEFERRED SUBMITTAL. 107 3.4.2. COMPREHENSIVE ENERGY |
| | SERVICES HAS REQUESTED THAT THE PRE-ENGINEERED STAND TO |
| | BE SUBMITTED BY THE GENERAL CONTRACTOR UNDER SEPARATE |
| | COVER (A DIFFERENT SUBMITTAL TRACKING NUMBER) IT IS NOT |
| | PART OF THEIR PERMIT PACKAGE. |
| | THE FLORIDA APPROVAL FL#16921.1-R2 IS MISSING THE |
| | FLORIDA APPROVAL COVERSHEETS AND ONLY ONE APPROVAL WAS |
| | SUBMITTED. 107.1 GENERAL. SUBMITTAL DOCUMENTS |
| | CONSISTING OF CONSTRUCTION DOCUMENTS, STATEMENT OF |
| | SPECIAL INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA |
| | SHALL BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT |
| | APPLICATION. |
| | |
| | 3) DEFERRED SUBMITTAL. 107 3.4.2. COMPREHENSIVE ENERGY |
| | SERVICES HAS REQUESTED THAT THE PRE-ENGINEERED STAND TO |
| | BE SUBMITTED BY THE GENERAL CONTRACTOR UNDER SEPARATE |
| | COVER (A DIFFERENT SUBMITTAL TRACKING NUMBER) IT IS NOT |
| | PART OF THEIR PERMIT PACKAGE. |
| | THE FLORIDA APPROVAL FL#16921.1-R2 HAS NOT BEEN |
| | REVIEWED, NEITHER THE CONTRACTOR NOR THE DESIGNER OF |
| | RECORD HAVE FOLLOWED THE PRODUCT APPROVAL IN |
| | CALCULATING THE AREA OF THE ROOF TOP COMPRESSORS, THE |
| | MEAN ROOF HEIGHT OF THE STAND AND COMPRESSORS, WEIGHT, |
| | CIRCLED THE DESIGN PARAMETERS IN THE TABLES , ANCHORS |
| | AND UPLIFT VERSES MOMENT. |
| | |
| | 4) DEFERRED SUBMITTAL. 107 3.4.2. COMPREHENSIVE ENERGY |
| | SERVICES HAS REQUESTED THAT THE PRE-ENGINEERED STAND TO |
| | BE SUBMITTED BY THE GENERAL CONTRACTOR UNDER SEPARATE |
| | COVER (A DIFFERENT SUBMITTAL TRACKING NUMBER) IT IS NOT |
| | PART OF THEIR PERMIT PACKAGE. |
| | THE FLORIDA APPROVAL FL#16921.1-R2 HAS NOT BEEN |
| | REVIEWED BY THE STRUCTURAL ENGINEER OF RECORD, NOR |
| | THEIR SHOP DRAWING STAMP OF APPROVAL APPLIED. |
| | FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH |
| | ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR |
| | TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL |
| | 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING |
| | DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE |
| | DELEGATED ENGINEER SHALL FORWARD THE DELEGATED |
| | ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR |
| | REVIEW. |
| | |
| | 5) COMPLIED. 2SETS OF PLANS SUBMITTED. NOTE (1) SET OF |
| | MASTER BUILT PLAN FOR ROOFTOP UNITS WAS SUPPLIED, (2) |
| | REQUIRED ADMINISTRATIVE CODE 107.1. |
| | |
| | 6) 2ND REQUEST. THE ISSUE WITH THE DESIGN IS THE RISK |
| | CATEGORY ASSIGNED FOR THE BUILDING. THE PLANS INDICATE |
| | A RISK CATEGORY FOR THE BUILDING I WHICH IS FOR THE |
| | LOCATION 156 VULT CORRECT. IN THE 2014 FBC-B TABLE |
| | 1604.5 CATEGORY I BUILDINGS ARE MINOR STORAGE |
| | FACILITIES, AGRICULTURAL FACILITIES, BARNS SILOS, ETC. |
| | OR SCREEN ENCLOSURES. THE RISK CATEGORY FOR THIS |
| | STRUCTURE IS A II PER 2014 FBC-B TABLE 1604.5 AND THE |
| | WIND SPEED IS 170 VULT (FIGURE 1609A). YOU ARE ALLOWED |
| | TO INTERPOLATE BETWEEN THE WIND SPEED LINES, BUT THE |
| | BUILDING IS A RISK CATEGORY II , TABLE 1604.5 2014 |
| | FBC-B. |
| | |
| | 1ST ROUND OF COMMENTS. MATER BUILT PLAN SUBMITTED |
| | INDICATES THE DESIGN IS FOR 165 VULT FOR THE ROOF TOP |
| | UNIT. SHEET S1 SHOWS AN VULT WIND SPEED OF 168, 3 |
| | SECOND GUST FOR THE WIND SPEED AT THIS LOCATION. |
| | |
| | 7) COMPLIED. FLORIDA P.E. SIGNED THE PLANS WITH FLORIDA |
| | SEAL |
| | |
| | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLATE AND STAPLE INTO SETS OF PLANS . A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | |