| 2017-03-14 09:31:46 | NFPA 14-6.4, 2012 FIRE DEPARTMENT CONNECTIONS. SHALL BE |
| | LOCATED NOT MORE THAN 100 FT (30.5 M) FROM THE NEAREST |
| | FIRE HYDRANT CONNECTED TO AN APPROVED WATER SUPPLY. |
| | 6.4.5.4.1 THE LOCATION OF THE FIRE DEPARTMENT |
| | CONNECTION SHALL BE PERMITTED TO EXCEED 100 FT (30.5 M) |
| | SUBJECT TO THE APPROVAL OF THE AUTHORITY HAVING |
| | JURISDICTION. |
| | |
| | FIRE PUMP INTALLATION SHALL COME IN COMPLIANCE WITH |
| | NFPA 20. |
| | |
| | NFPA 72-5.15 SUPERVISORY SIGNAL-INITIATING DEVICES: |
| | 5.15.1 CONTROL VALVE SUPERVISORY SIGNAL-INITIATING |
| | DEVICE. 5.15.1.1 TWO SEPARATE AND DISTINCT SIGNALS |
| | SHALL BE INITIATED: ONE INDICATING MOVEMENT OF THE |
| | VALVE FROM ITS NORMAL POSITION (OFF-NORMAL) AND THE |
| | OTHER INDICATING RESTORATION OF THE VALVE TO ITS NORMAL |
| | POSITION. |
| | |
| | 5.15.1.2 THE OFF-NORMAL SIGNAL SHALL BE INITIATED |
| | DURING THE FIRST TWO REVOLUTIONS OF THE HAND WHEEL OR |
| | DURING ONE-FIFTH OF THE TRAVEL DISTANCE OF THE VALVE |
| | CONTROL APPARATUS FROM ITS NORMAL POSITION. 5.15.1.3 |
| | THE OFF-NORMAL SIGNAL SHALL NOT BE RESTORED AT ANY |
| | VALVE POSITION EXCEPT NORMAL. 5.15.1.4 AN INITIATING |
| | DEVICE FOR SUPERVISING THE POSITION OF A CONTROL VALVE |
| | SHALL NOT INTERFERE WITH THE OPERATION OF THE VALVE, |
| | OBSTRUCT THE VIEW OF ITS INDICATOR, OR PREVENT ACCESS |
| | FOR VALVE MAINTENANCE. |
| | |