| Plan Review Notes For Permit 17010155 |
| Permit Number |
17010155 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-01-18 15:10:45 | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | 1] ELECTRICAL REVIEW UNDER 16120490 | | | | | | 2] CONDENSER UNIT REQUIRESA SERVICE GFCI RECEPTACLE | | | OUTLET WITHIN 25' OF EQUIPMENT PER FBC-R SEC E3901.11 | | | (PROVISO COMMENT) | | | | | | 3] PROVIDE A DISCONNECT WITHIN SIGHT OF THE CONDENSER | | | UNIT PER FBC-R SEC E4101.5 (PROVISO COMMENT) |
|