| 2017-01-09 09:43:49 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17010134 | | | 1/9/17 | | | | | | 1) SHOW THE LOCATION OF KEY NOTE #10. | | | | | | 2) PROVIDE AUTOMATIC SHUTOFF DAMPERS FOR THE O/A DUCTS | | | TO AHU- 1 & 2. | | | | | | 3) PROVIDE A REVISED ELECTRICAL PLAN. | | | | | | 4) PROVIDE A NARRATIVE THAT CLARIFES THE SCOPE OF THE | | | PLAN REVISIONS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|