2017-05-24 18:14:151ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: NOT COMPLIED 2ND REQUEST.
  
 A RAIN SENSOR AND CONTROLLER IS REQUIRED ON THE
 IRRIGATION SYSTEM PER FL. STATUTE 373.62.
 2) A BACKFLOW PREVENTION DEVICE IS REQUIRED ON THE
 WATER SUPPLY TO THE IRRIGATION SYSTEM PER THE CITY OF
 WPB CROSS- CONNECTION CONTROL MANUAL & 2014
 FBC-PLUMBING SEC.608.16.5.
 3) THE BACKFLOW DEVICE SHALL BE LEAD FREE AND A
 SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW DEVICE.
 2014 FBC-PLUMBING SEC.605.2.1.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  