| 2017-05-24 18:14:15 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: NOT COMPLIED 2ND REQUEST. | | | | | | A RAIN SENSOR AND CONTROLLER IS REQUIRED ON THE | | | IRRIGATION SYSTEM PER FL. STATUTE 373.62. | | | 2) A BACKFLOW PREVENTION DEVICE IS REQUIRED ON THE | | | WATER SUPPLY TO THE IRRIGATION SYSTEM PER THE CITY OF | | | WPB CROSS- CONNECTION CONTROL MANUAL & 2014 | | | FBC-PLUMBING SEC.608.16.5. | | | 3) THE BACKFLOW DEVICE SHALL BE LEAD FREE AND A | | | SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW DEVICE. | | | 2014 FBC-PLUMBING SEC.605.2.1. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|