2017-05-24 18:16:141ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: HAS NOT COMPLIED 2ND REQUEST
  
 1) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 58, AND FBC-2014 FUEL
 GAS CODE SEC. 402.2, AND 301.3. GAS APPLIANCES SHALL BE
 LISTED AND LABELED. THE INSTALLATION MANUALS FOR ALL
 GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME
 OF INSPECTION. FGC SEC.305.1,
  
 3) SHOW THE METHOD OF REQUIRED PROTECTION FOR THE LP
 TANK AND APPURTENANCES PER NFPA 58.
  
 5) STATIONARY ENGINE GENERATOR ASSEMBLIES SHALL MEET
 THE REQUIREMENTS OF UL 2200 AND NFPA 37.. SUBMIT MANUF.
 SPECIFICATIONS FOR REVIEW. 2014 FGC SEC.616.1.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  