Plan Review Notes
Plan Review Notes For Permit 17010126
Permit Number 17010126
Review Stop B
Sequence Number 1
Notes
Date Text
2017-01-23 09:33:02BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17010126
 ADD: 3199 CUMBERLAND DRIVE
 CONT: J. COMPTON ELECTRIC, INC.
 TEL: 561-588-6559
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JAN. 23/2017
 ACTION: DENIED
  
 1) COMPLIED. CONCRETE PAD AND TELELECTRONIC EQUIPMENT
 RACKS.
  
 2) THE WIND DESIGN CRITERIA SHOWS THIS BUILDING IS 160
 MPH. PLEASE REFER TO TABLE 1604.5 RISK CATEGORY OF
 BUILDINGS AND OTHER STRUCTURES. THE BUILDING RISK
 CATEGORY INDICATED ON THE PLANS IS RISK CATEGORY II
 WITH A 170 VULT WIND DESIGN, THIS STRUCTURE IS NOT
 AGRICULTURAL OUT BUILDING NOT A TEMPORARY FACILITY,
 MINOR STORAGE FACILITY NOR SCREEN ENCLOSURE. AFTER THE
 2004 & 2005 HURRICANES WE WERE REQUIRING THE CELL
 TOWERS TO BE CLASSIFIED AS A RISK CATEGORY III. THROUGH
 THE APPLICANT A LETTER CAME BACK FROM THE STATE THAT
 THE CELL TOWERS AND ASSOCIATED EQUIPMENT WAS TO BE
 INTERPRETED AS A RISK CATEGORY II NOT AN III. PLEASE
 CORRECT THE WIND SPEED.
  
 3) SHEET C-6 SHOWS AN ANCHORING DETAIL. THIS DETAIL
 WILL NEED TO BE RE-EVALUATED FOR A 170 VULT MPH WIND
 SPEED. TABLE 1604.5 AND FIGURE 1609 A RISK CATEGORY II
 BUILDINGS.
  
 4) SHEET C-5 THE ATTENDANT UTILITIES PROPANE GAS TANK
 AND METAL GENERATOR ENCLOSURE SHOW ANCHORING DETAILS
 BUT THERE IS NO WIND DESIGN AS TO WHAT WIND SPEED. 2014
 FBC-B 1603.1.4 WIND DESIGN DATA.
  
 5) SHEET C-2 AND OTHER SHEETS SHOWING AN ELEVATION.
 THROUGHOUT THE SET OF PLANS ELEVATION IS GIVEN IN THE
 TERMS NAVD 88. THE CITY AND ALL FLOOD MAPS ADOPTED ARE
 STILL USING NGVD 29 PLEASE CORRECT ELEVATIONS, OR SHOW
 THE EQUIVALENCY IN NGVD. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 6) REPORT TRANSMISSION LINE PROJECT T00000016270 BY
 JASON TRUCKENBROD, P. E. IS A COPY OF SIGNATURE AND
 SEAL.
 61G15-23.001 ENGINEERS SEALS ACCEPTABLE TO THE BOARD.
 SAID SEAL SHALL BE A MINIMUM OF 1 7/8 INCHES IN
 DIAMETER, TO SAY LICENSE NOT CERTIFICATE. ALL ENGINEERS
 MUST BE UTILIZING SAID SEAL NO LATER THAN JANUARY 1,
 2006.
  
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
  
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 EFFECTIVE DATE 05/06/2009. (2)(A) EVERY SHEET OF PLANS
 AND PRINTS WHICH MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471, F.S., SHALL BE SEALED, SIGNED AND DATED BY
 THE PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
  
 7) REPORT TRANSMISSION LINE PROJECT T00000016270
 INDICATES ATTACHED FOUNDATION REPORT FOR CALCULATIONS
 OF THE REQUIRED SET DEPTH AND BACKFILL. NO SUCH
 CALCULATIONS ARE FOUND IN REPORT, NOTE TO BE SIGNED AND
 SEALED BY THE ENGINEER OF CALCULATIONS. 61G15-23.002(2)
 FL. ADMIN. CODE. A COVER SHEET OR INDEX SHEET FOR
 ENGINEERING SPECIFICATIONS MAY BE USED AND THAT SHEET
 MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE PRODUCTION
 & PREPARATION OF EACH SECTION OF THE ENGINEERING
 SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER
 SHEET OR INDEX LISTING HOW MANY PAGES ARE COVERED UNDER
 THE COVER SHEET OR INDEX SHEET. .
 8) PLEASE INDICATE HOW THE FOUNDATION DESIGN WAS
 DERIVED WITHOUT A SOILS REPORT? 1803.5.2 QUESTIONABLE
 SOIL.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  