| Plan Review Notes For Permit 17010106 |
| Permit Number |
17010106 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-01-09 11:54:45 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: PARENTHESIS | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | | | | 1) SHEET LS 1 - THERE IS AN INCORRECT REFERENCE TO THE | | | APPLICABLE EDITION OF THE CURRENT FIRE CODE. IN NOTE | | | BOX "CLASSIFICATION OF HAZARDOUS CONTENTS" IT IS | | | INDICATED FFPC 2010 AND NFPA 101 2009. | | | | | | THE CURRENT EDITION OF THE FFPC INCLUDING NFPA 1 & 101 | | | IS 2012. THIS DOES APPEAR TO NEGATIVELY AFFECT YOUR | | | SUBMITTAL. | | | | | | PLEASE ENSURE COMPLIANCE AND UPDATE YOUR RECORDS FOR | | | FUTURE SUBMITTALS. | | | | | | | | | | | | 2) SHEET LS 1 & E 2.01 - THE LIFE SAFETY SYSTEMS, FIRE | | | ALARM AND/OR FIRE SPRINKLER SHALL REMAIN ACTIVE | | | THROUGHOUT THE CONSTRUCTION PERIOD. | | | | | | ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER | | | SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND | | | BY CERTIFIED LIFE SAFETY CONTRACTORS. | | | | | | ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, | | | SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE | | | WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL | | | AND COMPLETE PROTECTION IS RETURNED. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | |
|