Plan Review Notes
Plan Review Notes For Permit 17010106
Permit Number 17010106
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-01-09 11:54:45THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: PARENTHESIS
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) SHEET LS 1 - THERE IS AN INCORRECT REFERENCE TO THE
 APPLICABLE EDITION OF THE CURRENT FIRE CODE. IN NOTE
 BOX "CLASSIFICATION OF HAZARDOUS CONTENTS" IT IS
 INDICATED FFPC 2010 AND NFPA 101 2009.
  
 THE CURRENT EDITION OF THE FFPC INCLUDING NFPA 1 & 101
 IS 2012. THIS DOES APPEAR TO NEGATIVELY AFFECT YOUR
 SUBMITTAL.
  
 PLEASE ENSURE COMPLIANCE AND UPDATE YOUR RECORDS FOR
 FUTURE SUBMITTALS.
  
  
  
 2) SHEET LS 1 & E 2.01 - THE LIFE SAFETY SYSTEMS, FIRE
 ALARM AND/OR FIRE SPRINKLER SHALL REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  