Plan Review Notes
Plan Review Notes For Permit 17010106
Permit Number 17010106
Review Stop B
Sequence Number 1
Notes
Date Text
2017-01-11 10:11:06BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17010106
 ADD: 901 45TH ST. / X-RAY ROOM- T1093
 CONT: WESTBROOKE CORP.
 TEL: 561-395-4126
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JAN. 11/ 2017
 ACTION: DENIED
  
 1) THE ARCHITECTURAL SHEETS IN ALL (3) SETS HAVE BEEN
 SEALED WITH AN IMPRESSION TYPE SEAL SO LIGHT THAT MANY
 OF THE SHEETS THE AUTHENTICITY OF THE SEAL CANNOT BE
 DETERMINED BY NAME OR REGISTRATION NUMBER.
 FLORIDA STATUTE 481.221?SEALS; DISPLAY OF CERTIFICATE
 NUMBER. THE SIGNATURE, DATE, AND SEAL SHALL BE EVIDENCE
 OF THE AUTHENTICITY OF THAT TO WHICH THEY ARE AFFIXED.
  
 2) THE STRUCTURAL SHEETS S1 & S2 ARE CREATED BY GE
 HEALTHCARE IMPLEMENTATION ? DESIGN CENTER. WHILE THE
 NAME OF THE COMPANY DOES NOT STATE ?ENGINEERING? USING
 THE NAMING CONVENTION DESIGN CENTER AND THE NOTES ON
 THE SHEET IT SUGGEST THERE IS OR WAS ENGINEERING
 COMPLETED TO KNOW WHAT POUNDAGE EACH OF THE ANCHORS HAS
 TO HOLD (NOTE # 2). THE SHEET S1 NOR S2 SHOW HOW THE
 LOADS WERE CALCULATED AS EITHER 1607.3 UNIFORM LIVE
 LOADS, OR 1607.4 CONCENTRATED LIVE LOADS. 1607.2 LOADS
 NOT SPECIFIED. FOR OCCUPANCIES OR USES NOT DESIGNATED
 IN TABLE 1607.1, THE LIVE LOAD SHALL BE DETERMINED IN
 ACCORDANCE WITH A METHOD APPROVED BY THE BUILDING
 OFFICIAL.
 1607.9.2 MACHINERY. FOR THE PURPOSE OF DESIGN, THE
 WEIGHT OF MACHINERY AND MOVING LOADS SHALL BE INCREASED
 AS FOLLOWS TO ALLOW FOR IMPACT: (1) LIGHT MACHINERY,
 SHAFT OR MOTOR-DRIVEN, 20 PERCENT; AND (2)
 RECIPROCATING MACHINERY OR POWER-DRIVEN UNITS, 50
 PERCENT. PERCENTAGES SHALL BE INCREASED WHERE SPECIFIED
 BY THE MANUFACTURER.
  
 NOTE # 2 GOES ON TO STATE NOT TO USE SCREW ANCHORS IN
 DIRECT TENSION.
  
 THE STRUCTURAL SHEETS S1 & S2 WHO IS TAKING THE
 RESPONSIBILITY THE DESIGN, THERE IS NO DESIGN
 PROFESSIONAL WHO TAKES THE RESPONSIBILITY FOR THE
 DESIGN, THERE IS NO ENGINEERING SHOWING HOW THE DESIGN
 OF 350 LBS. EVERY 2 FOOT 2 INCHES? FLORIDA STATUTES 471
 ENGINEERING & 481 ARCHITECTURE.
  
 IN THE ANCHORS BEING CAPABLE OF WITHSTANDING 350 LBS.
 THERE IS A SAFETY FACTOR THAT IS NOT KNOWN NOR IS THERE
 ANY REFERENCES TO STANDARDS, CODE SECTIONS TO EITHER
 THE
  
 THIS SHEET SHOULD EITHER BE DESIGNED BY AN ENGINEER, OR
 A DELEGATE ENGINEER AND REVIEWED BY THE FLORIDA
 ENGINEER OF RECORD OR BE BROUGHT IN AS A SHOP DRAWING
 TO BE REVIEWED BY THE ARCHITECT OF RECORD AND THEIR
 SHOP DRAWING STAMP OF APPROVAL AFFIXED TO THE PLAN. FL
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC...
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  