| Plan Review Notes For Permit 17010099 |
| Permit Number |
17010099 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-04-11 11:55:50 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #17010099 | | | 4/11/17 | | | | | | 1) SHEET M002: THE O/A CALCULATION FOR AC-9 IS NOT IN | | | COMPLIANCE WITH ASHRAE 62.1-2010 WHICH REQUIRES AN | | | OCCUPANCY DENSITY OF 150 PERSONS PER 1000 S.F.- PLEASE | | | CORRECT BOTH THE O/A CALCULATIONS AND THE AC COOLING | | | AND HEATING CALCULATIONS. PLEASE NOTE THAT THE AC | | | CACLULATIONS FOR THE NEW SYSTEMS WERE NOT RETURNED WITH | | | THE CORRECTED PLANS. | | | | | | 2) THE REQUESTED SPECIFICATIONS FOR THE OVEN AND HOOD | | | WERE NOT SUBMITTED. PLEASE NOTE THAT THE WPB | | | CONSTRUCTION SERVICES DIVISION REQUIRES KITCHEN HOODS | | | TO BE SUBMITTED UNDER A SEPARATE PERMIT. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|