| Plan Review Notes For Permit 17010099 |
| Permit Number |
17010099 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-01-25 17:54:31 | 1ST REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1. GRAB BARS SHALL BE MEASURED FROM FINISHED FLOOR TO | | | THE TOP OF GRIPPING SURFACE. PER FBC ACC 609.4 | | | | | | 2. THE TOILETPAPER DISPENSER SHALL BE 7"- 9" MEASURED | | | FROM THE FRONT OF THE TOILET TO THE CENTER OF THE | | | DISPENSER. PER FBC ACC 604.7 | | | | | | 3. ONE URINAL SHALL BE ACCESSIBLE WITH THE RIM AT 17" | | | MAX OFF FINISHED FLOOR AND HAVE A CLEAR FLOOR SPACE OF | | | 30" X 48" PER FBC ACC 605 | | | | | | 4. SHT. P102 SHOW EXACTLY WHERE THE EXISTING GREASE | | | LINES WILL BE CAPPED NO DEAD ARE PERMITTED. PER WPB | | | AMEND TO FBC | | | | | | 5. ARE THE BATHROOMS 110 + 111 UNDER THIS PERMIT THE | | | COVER SHEETS SHOWS THEM UNDER A DIFFERENT PHASE PLEASE | | | CLARIFY. PER WPB AMEND TO FBC | | | | | | 6. THE LAVATORY'S ARE REQUIRED TO HAVE TEMPERED WATER. | | | PER FBC PL 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING | | | FACILITIES. | | | TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND | | | GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES | | | PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED | | | WATER SHALL BE DELIVERED THROUGH AN APPROVED | | | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE | | | 1070 OR CSA B125.3. | | | | | | 7. SHT S201 SHOWS FD IN BATHROOMS 126+127 THEY ARE NOT | | | SHOWN ON THE PLUMBING PLANS PLEASE CLARIFY. PER WPB | | | AMEND TO FBC |
|