Plan Review Notes
Plan Review Notes For Permit 17010099
Permit Number 17010099
Review Stop P
Sequence Number 1
Notes
Date Text
2017-01-25 17:54:311ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. GRAB BARS SHALL BE MEASURED FROM FINISHED FLOOR TO
 THE TOP OF GRIPPING SURFACE. PER FBC ACC 609.4
  
 2. THE TOILETPAPER DISPENSER SHALL BE 7"- 9" MEASURED
 FROM THE FRONT OF THE TOILET TO THE CENTER OF THE
 DISPENSER. PER FBC ACC 604.7
  
 3. ONE URINAL SHALL BE ACCESSIBLE WITH THE RIM AT 17"
 MAX OFF FINISHED FLOOR AND HAVE A CLEAR FLOOR SPACE OF
 30" X 48" PER FBC ACC 605
  
 4. SHT. P102 SHOW EXACTLY WHERE THE EXISTING GREASE
 LINES WILL BE CAPPED NO DEAD ARE PERMITTED. PER WPB
 AMEND TO FBC
  
 5. ARE THE BATHROOMS 110 + 111 UNDER THIS PERMIT THE
 COVER SHEETS SHOWS THEM UNDER A DIFFERENT PHASE PLEASE
 CLARIFY. PER WPB AMEND TO FBC
  
 6. THE LAVATORY'S ARE REQUIRED TO HAVE TEMPERED WATER.
 PER FBC PL 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING
 FACILITIES.
 TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.
  
 7. SHT S201 SHOWS FD IN BATHROOMS 126+127 THEY ARE NOT
 SHOWN ON THE PLUMBING PLANS PLEASE CLARIFY. PER WPB
 AMEND TO FBC