2017-01-25 10:08:561ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17010099
 1/25/17
  
 1) PROVIDE FIRE DAMPERS FOR DUCTS PENETRATING THE
 FLOOR/CEILING ASSEMBLIE SBETWEEN THE FIRST AND SECOND
 LEVELS- SECTION 607.6.2.
  
 2) M103: SHOW THE LOCATIONS OF THE REQUIRED DUCT SMOKE
 DETECTORS IN THE RETURN AIR SYSTEMS OF THE AC UNITS-
 SECTION 606.2.1
  
 3) M104: THERE APPEARS TO BE A ROOM OR SPACE ON THE
 SECOND FLOOR ABOVE THE NEW FIRST FLOOR KITCHEN AND
 MEETING ROOM THAT IS NO LONGER BEING CONDITIONED-
 PLEASE CLARIFY.
  
 4) REFER TO TABLE 403.3 AND PROVIDE AN EXHAUST
 VENTILATION CALCULATION FOR THE KITCHEN.
  
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE OVEN
 AND HOOD.
  