Plan Review Notes
Plan Review Notes For Permit 17010099
Permit Number 17010099
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-01-10 11:44:31THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET T 101 - THERE ARE INCORRECT REFERENCES TO THE
 CURRENT FIRE CODES INDICATED.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
 CLEAN AGENT SYSTEMS SHALL COMPLY WITH NFPA 2001, 2012
 EDITION.
 EMERGENCY AND STANDBY POWER SYSTEMS SHALL COMPLY WITH
 NFPA 110, 2013 EDITION.
 COMMERCIAL COOKING SHALL COMPLY WITH NFPA 96, 2011
 EDITION.
  
 PLEASE CORRECT AND ENSURE COMPLIANCE.
  
  
  
 2) SHEET T 101 - THERE IS NO ADDRESS INDICATED IN THE
 TITLE BLOCK.
  
 FOR SPECIFIC LOCATION PURPOSES, PLEASE PROVIDE THE
 ADDRESS OF THE PROJECT IN THE TITEL BLOCK.
  
  
  
 3) NO SHEET - PLEASE PROVIDE A COMPLETE LIFE SAFETY
 PLAN THAT ILLUSTRATES OCCUPANT LOADS, TRAVEL DISTANCES,
 COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS,
 EMERGENCY LIGHTING, EXITS LEADING TO A PUBLIC WAY, FIRE
 EXTINGUISHER LOCATIONS, AND ALL FIRE SAFETY FEATURES
 AND EQUIPMENT.
  
 PLEASE ENSURE, WITH SPECIFIC NARRATIVE OR DESIGN
 DRAWING, IF THE PROJECT PROPOSES TO BE ONGOING WITH
 OCCUPANCY OF THE GENERAL PUBLIC IN ADJACENT AREAS, HOW
 WILL THE PROJECT AREA BE PROTECTED/SEPARATED FROM
 ACCESS.
  
  
  
  
 4) SHEET A 101 - THERE ARE DASH LINES INDICATED AROUND
 THE KITCHEN AND PANTRY. THERE IS ALSO A NOTE INDICATED
 "FRP".
  
 PLEASE CLARIFY FRP AND IF IT IS FIRE RATED PROTECTION
 (OR SIMILAR), PLEASE INDICATE THE NUMERIC VALUE OF THE
 RATING.
  
  
  
 5) SHEET A 101 - A KITCHEN IS INDICATED. ANY KITCHEN
 EQUIPMENT SHALL BE INSTALLED PER THE APPLICABLE CODE
 UNDER SEPARATE SHOP DRAWINGS AND PERMIT.
  
 CHAPTER 9 BUILDING SERVICE AND FIRE PROTECTION
 EQUIPMENT
 9.2.3 COMMERCIAL COOKING EQUIPMENT. COMMERCIAL COOKING
 EQUIPMENT SHALL BE IN ACCORDANCE WITH NFPA 96, STANDARD
 FOR VENTILATION CONTROL AND FIRE PROTECTION OF
 COMMERCIAL COOKING OPERATIONS, UNLESS SUCH
 INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS,
 WHICH SHALL BE PERMITTED TO BE CONTINUED IN SERVICE.
  
 NFPA 96, CHAPTER 4 GENERAL REQUIREMENTS
 4.1 GENERAL.
 4.1.1 COOKING EQUIPMENT USED IN PROCESSES PRODUCING
 SMOKE OR GREASE-LADEN VAPORS SHALL BE EQUIPPED WITH AN
 EXHAUST SYSTEM THAT COMPLIES WITH ALL THE EQUIPMENT AND
 PERFORMANCE REQUIREMENTS OF THIS STANDARD.
 10.1.2* COOKING EQUIPMENT THAT PRODUCES GREASE-LADEN
 VAPORS AND THAT MIGHT BE A SOURCE OF IGNITION OF GREASE
 IN THE HOOD, GREASE REMOVAL DEVICE, OR DUCT SHALL BE
 PROTECTED BY FIRE-EXTINGUISHING EQUIPMENT.
  
 PLEASE ENSURE COMPLIANCE WITH THE ABOVE CODE.
  
  
  
 6) SHEET A 301 - SHOULD THE DASH LINES SHOWN ON SHEET A
 101 (#4 ABOVE) INDICATE A FIRE RATED WALLS THEN THE
 DOORS 117A, 117B, 120A, 118A, SHOULD BE FIRE RATED. THE
 DOOR SCHEULDE ON SHEET A 301 DO NOT INDICATE ANY RATING
 FOR THESE DOORS.
  
 PLEASE REVIEW, CLARFIY AND/OR CORRECT.
  
  
  
 7) SHEET FP 101 - WORK ON THE FIRE SPRINKLER SYSTEM IS
 INDICATED.
  
 PROVIDE A NOTE INDICATING:
  
 THE FIRE SPRINKLER SYSTEM SHALL REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE SPRINKLER SYSTEM SHALL BE
 DONE UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED LIFE
 SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE SPRINKLER SYSTEM EXCEEDS 4
 HOURS, A FIRE WATCH SHALL BE IMPLEMENTED AND MAINTAINED
 UNTIL FULL AND COMPLETE PROTECTION IS RETURNED.
  
  
 8) SHEET E 202 - WORK ON THE FIRE ALARM SYSTEM IS
 INDICATED.
  
 PROVIDE A NOTE INDICATING:
  
 THE FIRE ALARM SYSTEM SHALL REMAIN ACTIVE THROUGHOUT
 THE CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE
 UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED LIFE
 SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE ALARM SYSTEM EXCEEDS 4 HOURS,
 A FIRE WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL
 FULL AND COMPLETE PROTECTION IS RETURNED.
  
  
  
 9) SHEET 102 - IF THE NOTE ON SHEET A 101 (# 4 ABOVE)
 INDICATES A FIRE RATED PARTITION, THERE IS NO CAL-OUT
 DESIGN OR DRAWING INDICATING THE LISTING FOR THE WALL.
  
 PLEASE CLARIFY AND OR CORRECT.
  
  
  
 10) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 11) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  