| 2017-01-10 11:44:31 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) SHEET T 101 - THERE ARE INCORRECT REFERENCES TO THE |
| | CURRENT FIRE CODES INDICATED. |
| | |
| | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| | THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| | APPLICABLE CODES OR STANDARDS. |
| | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 13, 2010 EDITION. |
| | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 72, 2010 EDITION. |
| | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 241, 2009 EDITION. |
| | FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 10, 2010 EDITION. |
| | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION. |
| | CLEAN AGENT SYSTEMS SHALL COMPLY WITH NFPA 2001, 2012 |
| | EDITION. |
| | EMERGENCY AND STANDBY POWER SYSTEMS SHALL COMPLY WITH |
| | NFPA 110, 2013 EDITION. |
| | COMMERCIAL COOKING SHALL COMPLY WITH NFPA 96, 2011 |
| | EDITION. |
| | |
| | PLEASE CORRECT AND ENSURE COMPLIANCE. |
| | |
| | |
| | |
| | 2) SHEET T 101 - THERE IS NO ADDRESS INDICATED IN THE |
| | TITLE BLOCK. |
| | |
| | FOR SPECIFIC LOCATION PURPOSES, PLEASE PROVIDE THE |
| | ADDRESS OF THE PROJECT IN THE TITEL BLOCK. |
| | |
| | |
| | |
| | 3) NO SHEET - PLEASE PROVIDE A COMPLETE LIFE SAFETY |
| | PLAN THAT ILLUSTRATES OCCUPANT LOADS, TRAVEL DISTANCES, |
| | COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS, |
| | EMERGENCY LIGHTING, EXITS LEADING TO A PUBLIC WAY, FIRE |
| | EXTINGUISHER LOCATIONS, AND ALL FIRE SAFETY FEATURES |
| | AND EQUIPMENT. |
| | |
| | PLEASE ENSURE, WITH SPECIFIC NARRATIVE OR DESIGN |
| | DRAWING, IF THE PROJECT PROPOSES TO BE ONGOING WITH |
| | OCCUPANCY OF THE GENERAL PUBLIC IN ADJACENT AREAS, HOW |
| | WILL THE PROJECT AREA BE PROTECTED/SEPARATED FROM |
| | ACCESS. |
| | |
| | |
| | |
| | |
| | 4) SHEET A 101 - THERE ARE DASH LINES INDICATED AROUND |
| | THE KITCHEN AND PANTRY. THERE IS ALSO A NOTE INDICATED |
| | "FRP". |
| | |
| | PLEASE CLARIFY FRP AND IF IT IS FIRE RATED PROTECTION |
| | (OR SIMILAR), PLEASE INDICATE THE NUMERIC VALUE OF THE |
| | RATING. |
| | |
| | |
| | |
| | 5) SHEET A 101 - A KITCHEN IS INDICATED. ANY KITCHEN |
| | EQUIPMENT SHALL BE INSTALLED PER THE APPLICABLE CODE |
| | UNDER SEPARATE SHOP DRAWINGS AND PERMIT. |
| | |
| | CHAPTER 9 BUILDING SERVICE AND FIRE PROTECTION |
| | EQUIPMENT |
| | 9.2.3 COMMERCIAL COOKING EQUIPMENT. COMMERCIAL COOKING |
| | EQUIPMENT SHALL BE IN ACCORDANCE WITH NFPA 96, STANDARD |
| | FOR VENTILATION CONTROL AND FIRE PROTECTION OF |
| | COMMERCIAL COOKING OPERATIONS, UNLESS SUCH |
| | INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS, |
| | WHICH SHALL BE PERMITTED TO BE CONTINUED IN SERVICE. |
| | |
| | NFPA 96, CHAPTER 4 GENERAL REQUIREMENTS |
| | 4.1 GENERAL. |
| | 4.1.1 COOKING EQUIPMENT USED IN PROCESSES PRODUCING |
| | SMOKE OR GREASE-LADEN VAPORS SHALL BE EQUIPPED WITH AN |
| | EXHAUST SYSTEM THAT COMPLIES WITH ALL THE EQUIPMENT AND |
| | PERFORMANCE REQUIREMENTS OF THIS STANDARD. |
| | 10.1.2* COOKING EQUIPMENT THAT PRODUCES GREASE-LADEN |
| | VAPORS AND THAT MIGHT BE A SOURCE OF IGNITION OF GREASE |
| | IN THE HOOD, GREASE REMOVAL DEVICE, OR DUCT SHALL BE |
| | PROTECTED BY FIRE-EXTINGUISHING EQUIPMENT. |
| | |
| | PLEASE ENSURE COMPLIANCE WITH THE ABOVE CODE. |
| | |
| | |
| | |
| | 6) SHEET A 301 - SHOULD THE DASH LINES SHOWN ON SHEET A |
| | 101 (#4 ABOVE) INDICATE A FIRE RATED WALLS THEN THE |
| | DOORS 117A, 117B, 120A, 118A, SHOULD BE FIRE RATED. THE |
| | DOOR SCHEULDE ON SHEET A 301 DO NOT INDICATE ANY RATING |
| | FOR THESE DOORS. |
| | |
| | PLEASE REVIEW, CLARFIY AND/OR CORRECT. |
| | |
| | |
| | |
| | 7) SHEET FP 101 - WORK ON THE FIRE SPRINKLER SYSTEM IS |
| | INDICATED. |
| | |
| | PROVIDE A NOTE INDICATING: |
| | |
| | THE FIRE SPRINKLER SYSTEM SHALL REMAIN ACTIVE |
| | THROUGHOUT THE CONSTRUCTION PERIOD. |
| | ANY AND ALL WORK ON THE FIRE SPRINKLER SYSTEM SHALL BE |
| | DONE UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED LIFE |
| | SAFETY CONTRACTORS. |
| | ANY TIME THAT WORK ON THE SPRINKLER SYSTEM EXCEEDS 4 |
| | HOURS, A FIRE WATCH SHALL BE IMPLEMENTED AND MAINTAINED |
| | UNTIL FULL AND COMPLETE PROTECTION IS RETURNED. |
| | |
| | |
| | 8) SHEET E 202 - WORK ON THE FIRE ALARM SYSTEM IS |
| | INDICATED. |
| | |
| | PROVIDE A NOTE INDICATING: |
| | |
| | THE FIRE ALARM SYSTEM SHALL REMAIN ACTIVE THROUGHOUT |
| | THE CONSTRUCTION PERIOD. |
| | ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE |
| | UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED LIFE |
| | SAFETY CONTRACTORS. |
| | ANY TIME THAT WORK ON THE ALARM SYSTEM EXCEEDS 4 HOURS, |
| | A FIRE WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL |
| | FULL AND COMPLETE PROTECTION IS RETURNED. |
| | |
| | |
| | |
| | 9) SHEET 102 - IF THE NOTE ON SHEET A 101 (# 4 ABOVE) |
| | INDICATES A FIRE RATED PARTITION, THERE IS NO CAL-OUT |
| | DESIGN OR DRAWING INDICATING THE LISTING FOR THE WALL. |
| | |
| | PLEASE CLARIFY AND OR CORRECT. |
| | |
| | |
| | |
| | 10) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 11) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |