2017-01-31 09:53:26INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA SPECIFICATION SHEET SUBMITTALS FOR
 HOOD SYSTEMS AND ALL LOW VOLTAGE SYSTEMS TO INCLUDE BUT
 NOT LIMITED TO FIRE ALARM, CCTV, PHONE AND DATA,
 WIRELESS SYSTEMS, ETC. A NOTE WILL SUFFICE.
 2. PROVIDE A SHOW COMPLIANCE WITH FBC EC 405.7.3,
 405.7.4 SEE VERBIAGE IN THE CODE REGARDING VOLTAGE DROP
 AND COMPLETIONS DOCUMENTS.
 3. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO
 INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC
 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS DUE TO
 MODIFICATION; SEE VERBIAGE IN CODE.
 4. PLEASE ID SHUNT TRIP BREAKER AT THE PANELBOARD
 SCHEDULE K, FOR ALL DEVICES UNDER HOOD IN KITCHEN HOOD
 AREA. FBC 107.3.5
 5. ADDRESS FIRE AND MECHANICAL COMMENTS RELATED TO
 ELECTRICAL.
 6. PROVIDE A NOTE AT THE RISER TO INDICATE THAT NEW
 400AMP BREAKER IS TO BE LISTED FOR REPLACEMENT WITHIN
 CABINET WHERE EXISTING 600AMP IS LOCATED. NEC 110.3B
 7. PROVIDE A NOTE TO SHEET E201 FOR DIMMING PANEL TO
 INDICATE THAT REQUIRED LIGHTING LEVELS MUST NOT FALL
 UNDER REQUIRED LIFE SAFETY LEVELS. FBC 107.3.5
 8. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE