2017-01-18 13:41:53BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17010099
 ADD: 1111 S. FLAGLER DR.
 CONT: MYRICK GUROSKY & ASS.
 TEL: 205-313-3027
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JAN. 13/ 2017
 ACTION: DENIED
  
 1) SHEET T101:
 1A) THE TITLESHEET T101 UNDER THE HEADING OF ADOPTED
 CODES WILL NEED TO UPDATE THE DESIGN OF THE PLANS TO
 THE CURRENT ADOPTED FAMILY OF CODES. STATEWIDE ON JUNE
 30/2015 THE 5TH EDITION OF THE FLORIDA BUILDING CODE
 (2014) WAS ADOPTED. JULY 1/2016 THE 2016 SUPPLEMENTS OF
 THE FLORIDA BUILDING CODE WERE ALSO ADOPTED STATEWIDE.
 PLEASE CORRECT THE CODE ANALYSIS AND PLANS ACCORDINGLY.
  
 1B) THE ARCHITECTURAL, (IN) INTERIOR SECTIONS NOR THE
 STRUCTURAL SHEETS PROVIDE THE ADDRESS WITHIN THE
 TITLEBLOCK. 2014 FLORIDA BUILDING CODE W 2014 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS . CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION OF THE
 PROPOSED WORK.
  
 2) IN THIS PERMIT SUBMITTAL THERE ARE NO LIFE SAFETY
 PLANS FOR THE 1ST NOR 2ND FLOOR. SHEET A101 AND A102
 THE 1ST AND 2ND STORY FLOOR PLANS SHOW A FLOOR LAYOUT
 BUT NO LIFE SAFETY INFORMATION.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING (7) OCCUPANCY LOAD/EGRESS
 REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 DEAD END CORRIDORS
 STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
  
 2A) ROOMS # 1,2 & 3 ALL ARE ASSEMBLY USE ROOMS WITH
 OCCUPANT LOADS 50 OR MORE OCCUPANTS. TO THE NORTH OF
 THESE ROOMS THERE IS A SERVICE HALL. NOTE THERE ARE
 DOORWAYS THAT LEAD OUT OF THESE ROOMS INTO THE SERVICE
 HALL AND THEN TO THE EXTERIOR OF THE BUILDING. THERE IS
 NO INFORMATION AS TO WHERE THE EXIT DISCHARGE LEADS YOU
 IF THE DOOR OPENINGS ON THE NORTH SIDE OF THE 3
 ASSEMBLY ROOMS ARE TO BE CONSIDERED THE 2ND MEANS OF
 EGRESS. SEE FBC-B TABLE 1015.1. THE NAMING OF THIS
 SPACE A SERVICE HALL LEADS ONE TO THINK THIS MAY END UP
 AS A STORAGE ROOM FOR TABLES AND CHAIRS SEE FBC-B
 1014.2.(4) EGRESS SHALL NOT PASS THROUGH KITCHENS,
 STORAGE ROOMS, CLOSETS OR SPACES USED FOR SIMILAR
 PURPOSES.
  
 2B)(1) SHEET A101 DETAIL # 2 INDICATES A PLATFORM PLAN.
 PLEASE INDICATE THE USAGE OF THIS AREA. PLATFORMS ARE
 ASSOCIATED WITH EQUIPMENT AND OR MACHINERY SUCH AS AIR
 CONDITIONING UNITS? 2014 FBC-B 505.3 EQUIPMENT
 PLATFORMS.
  
 2B)(2) SHEET S102 DETAIL #2 SHOWS A PARTIAL PORTION OF
 THE PLATFORM OVER THE PANTRY. WITHIN THIS DETAIL THE
 LIVE LOAD DESIGN IS 125 LBS./ PSF WHICH IS THE DESIGN
 LOADS USED FOR STORAGE FOR LIGHT LOADS SEE FBC-B TABLE
 1607.1. IT WOULD APPEAR THE FLOOR LOADING IS BEING
 DESIGNED FOR A MEZZANINE USAGE LIGHT STORAGE WHEREAS
 THE LOADING INDICATED IN TABLE 1607.1 FOR ELEVATED
 PLATFORMS IS 60LBS./ PSF. ADDITIONAL INFORMATION IS
 REQUIRED 107.2.1.3.
  
 2C) SHEET S102 DETAIL #2 SHOWS A PARTIAL PORTION OF THE
 PLATFORM OVER THE PANTRY. THE PLANS DO NOT INDICATE IF
 THE OTHER SIDE OF THE PLATFORM WILL HAVE THE SAME
 VERTICAL FRAMING & FASTENING PATTERN. 107.2.1.3.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 2D) SHEET S-102 DETAIL # 2 SHOWS THE FLOOR FRAMING
 MEMBERS TO BE 10 INCH STEEL STUD FRAMING AT 16 INCHES
 ON CENTER. PLEASE REVIEW SHEET S-101 UNDER THE HEADING
 5.0 STEEL DECK SEE NOTES 5.2 THE FLOOR FRAMING IS TO BE
 LIGHT GAGE STEEL STUD FLOOR JOIST @ 1 FOOT O/C AT ALL
 SUPPORTS. DISCREPANCY IN PLANS 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED. THE VERTICAL WALL STEEL STUDS
 ARE AT 16 INCHES ON CENTER, THE COMMENT ABOVE (2C) THE
 ATTACHMENT METHOD OF THE HORIZONTAL TO VERTICAL STUDS
 WILL NOT LINE UP, NEW DETAIL WOULD BE REQUIRED. ALSO
 SEE SHEET S201 SHOWS THE FLOOR FRAMING @ 16 INCHES ON
 CENTER?
  
 2E) SHEET S102 DETAIL #2 SHOWS A PARTIAL PORTION OF THE
 PLATFORM OVER THE PANTRY. NOTE ON THIS DETAIL INDICATES
 THE FINAL DESIGN IS TO BE PROVIDED BY THE COLD STEEL
 FRAMING MANUFACTURER. IF THE DESIGN BY THE COLD STEEL
 FRAMING MANUFACTURER IS COMPLETED BY A DELEGATE
 ENGINEER THEN SHOW COMPLIANCE WITH:
 61G15-30.003 ENGINEERING DOCUMENT CLASSIFICATION. FL
 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL FORWARD
 THE DELEGATED ENGINEERING DOCUMENTS TO THE ENGINEER OF
 RECORD FOR REVIEW.
  
 2F) SHEET S102 DETAIL #2 SHOWS A PARTIAL PORTION OF THE
 PLATFORM OVER THE PANTRY. IF THE PLATFORM IS ACTUALLY A
 STORAGE MEZZANINE THEN SHOW COMPLIANCE WITH 2014
 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS
 TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION:
  
 106.1 LIVE LOADS POSTED. WHERE THE LIVE LOADS FOR WHICH
 EACH FLOOR OR PORTION THEREOF OF A
 COMMERCIAL OR INDUSTRIAL BUILDING IS OR HAS BEEN
 DESIGNED TO EXCEED 50 PSF (2.40 KN/M2), SUCH
 DESIGN LIVE LOADS SHALL BE CONSPICUOUSLY POSTED BY THE
 OWNER IN THAT PART OF EACH STORY IN WHICH THEY
 APPLY, USING DURABLE SIGNS. IT SHALL BE UNLAWFUL TO
 REMOVE OR DEFACE SUCH NOTICES.
  
 106.2 ISSUANCE OF CERTIFICATE OF OCCUPANCY. A
 CERTIFICATE OF OCCUPANCY REQUIRED BY SECTION 111
 SHALL NOT BE ISSUED UNTIL THE FLOOR LOAD SIGNS,
 REQUIRED BY SECTION 106.1, HAVE BEEN INSTALLED.
  
 106.3 RESTRICTIONS ON LOADING. IT SHALL BE UNLAWFUL TO
 PLACE, OR CAUSE OR PERMIT TO BE PLACED, ON
 ANY FLOOR OR ROOF OF A BUILDING, STRUCTURE OR PORTION
 THEREOF, A LOAD GREATER THAN IS PERMITTED BY THIS
 CODE.
  
 2G) SHEET S102 DETAIL #2 SHOWS A PARTIAL PORTION OF THE
 PLATFORM OVER THE PANTRY AND FOR ACCESS THE USE OF A
 SHIPS LADDER. PLEASE PROVIDE WHERE THE CODE ALLOWS FOR
 THE USE OF A SHIPS LADDER. 2014 FBC-B 1009.14 SHIPS
 LADDERS.
  
 3) SHEET D101 SHOWS THE DEMOLITION OF PORTIONS OF
 EXTERIOR CMU WALLS FOR NEW DOUBLE DOOR OPENINGS. ON
 SHEET S102 THERE IS A LINTEL SCHEDULE BUT NO SECTIONS
 SHOWING HOW THE NEW COLUMNS/ REBAR AND LINTELS ARE TO
 ATTACH TO THE FOOTERS NOR THE BEAM ABOVE TO CREATE A
 CONTINUOUS LOAD PATH AND BE PART OF THE MWFRS (MAIN
 WIND FORCE RESISTING SYSTEM). SHEET S102 SHOWS A SERIES
 OF DETAILS WITH ANGLES ACTING AS SUPPORT AT THE NEW
 DOOR OPENING BUT NO MENTION OF COLUMNS BEING ELIMINATED
 OR NOT. NO MENTION OF HOW THE BRICK VENEER ARE TO BE
 SUPPORTED BY STEEL ANGLE IRON SEE A201.
 IF MASONRY: 2104.1 MASONRY CONSTRUCTION. MASONRY
 CONSTRUCTION SHALL COMPLY WITH THE REQUIREMENTS OF
 SECTIONS 2104.1.1 THROUGH 2104.4 AND WITH TMS 602/ACI
 530.1/ASCE 6.
 IF COLUMNS ARE CONCRETE THEN: FBC-B 1901.2 REINFORCED
 CONCRETE.
  
 4) SHEETS A101, A201 & A301 ALL SHOW NEW EXTERIOR OR
 REPLACED WINDOWS AND DOORS. NEITHER THE ARCHITECTURAL
 SHEETS NOR THE STRUCTURAL SHEETS SHOW THE WIND DESIGN
 CRITERIA AND ASSOCIATED PRESSURES.
 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 4.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 4.2. RISK CATEGORY.
  
 4.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
  
 4.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 4.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 5) PLEASE PROVIDE DOCUMENTS INDICATING COMPLIANCE WITH:
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS,
  
 6) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) PLEASE SHOW COMPLIANCE WITH : 2014 FBC-ENERGY CODE
 C401.2.1 APPLICATION TO EXISTING BUILDINGS.
 ADDITIONS, ALTERATIONS AND REPAIRS TO EXISTING
 BUILDINGS SHALL COMPLY WITH ONE OF THE FOLLOWING:
 1. SECTIONS C402, C403, C404 AND C405; OR
 2. ANSI/ASHRAE/IESNA 90.1.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER