| Plan Review Notes For Permit 17010063 |
| Permit Number |
17010063 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2017-03-09 12:28:08 | 5011 BROADWAY - CITY MARKET | | | PERMIT #17010063 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | REPEAT COMMENT X3 | | | REVISE PERMIT VALUE: UNDERGROUND FIRELINE AND BACKFLOW | | | PREVENTER VALUE NEEDS TO BE ADDED TO THE FIRE SPRINKLER | | | PERMIT SO THE PROPER FEES CAN BE ASSESSED. ORIGINAL | | | COMMENT - SHEET FP1: PLANS INDICATE 4-INCH UNDERGROUND | | | FIRE MAIN IS TO BE INSTALLED BY OTHERS. IS THIS | | | CORRECT? IF YES, A SEPARATE UNDERGROUND FIRE LINE | | | PERMIT WILL BE NEEDED. | | | | | | REPEAT COMMENT X2 | | | PART OF THE ROOFING STRUCTURE IS CONSTRUCTED OF | | | COMBUSTIBLE CONSTRUCTION; HOWEVER, NO SPRINKLERS HAVE | | | BEEN PROVIDED IN THE COMBUSTIBLE CONCEALED SPACE PER | | | NFPA 13. | | | | | | REPEAT COMMENT X2 | | | THE HYDRAULIC AREA UTILIZES A SPRINKLER AREA OF 120 | | | SQUARE FEET PER SPRINKLER. PROVIDE HYDRAULIC | | | CALCULATIONS UTILIZING THE NORTHEAST COOLER AS THE | | | REMOTE SPRINKLER BECAUSE THIS SPRINKLER APPEARS TO BE | | | PROTECTING AN AREA OF 182 SQUARE FEET, THEREBY | | | REQUIRING A STARTING FLOW OF +36 GALLONS (182 X 0.2 | | | DENSITY). | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] |
|