2017-03-09 12:28:085011 BROADWAY - CITY MARKET
 PERMIT #17010063
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT X3
 REVISE PERMIT VALUE: UNDERGROUND FIRELINE AND BACKFLOW
 PREVENTER VALUE NEEDS TO BE ADDED TO THE FIRE SPRINKLER
 PERMIT SO THE PROPER FEES CAN BE ASSESSED. ORIGINAL
 COMMENT - SHEET FP1: PLANS INDICATE 4-INCH UNDERGROUND
 FIRE MAIN IS TO BE INSTALLED BY OTHERS. IS THIS
 CORRECT? IF YES, A SEPARATE UNDERGROUND FIRE LINE
 PERMIT WILL BE NEEDED.
  
 REPEAT COMMENT X2
 PART OF THE ROOFING STRUCTURE IS CONSTRUCTED OF
 COMBUSTIBLE CONSTRUCTION; HOWEVER, NO SPRINKLERS HAVE
 BEEN PROVIDED IN THE COMBUSTIBLE CONCEALED SPACE PER
 NFPA 13.
  
 REPEAT COMMENT X2
 THE HYDRAULIC AREA UTILIZES A SPRINKLER AREA OF 120
 SQUARE FEET PER SPRINKLER. PROVIDE HYDRAULIC
 CALCULATIONS UTILIZING THE NORTHEAST COOLER AS THE
 REMOTE SPRINKLER BECAUSE THIS SPRINKLER APPEARS TO BE
 PROTECTING AN AREA OF 182 SQUARE FEET, THEREBY
 REQUIRING A STARTING FLOW OF +36 GALLONS (182 X 0.2
 DENSITY).
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]