| 2017-02-15 15:25:35 | 5011 BROADWAY - CITY MARKET |
| | PERMIT #17010063 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | REVISE PERMIT VALUE: UNDERGROUND FIRELINE AND BACKFLOW |
| | PREVENTER VALUE NEEDS TO BE ADDED TO THE FIRE SPRINKLER |
| | PERMIT SO THE PROPER FEES CAN BE ASSESSED. ORIGINAL |
| | COMMENT - SHEET FP1: PLANS INDICATE 4-INCH UNDERGROUND |
| | FIRE MAIN IS TO BE INSTALLED BY OTHERS. IS THIS |
| | CORRECT? IF YES, A SEPARATE UNDERGROUND FIRE LINE |
| | PERMIT WILL BE NEEDED. |
| | |
| | REPEAT COMMENT: NO EQUIPMENT CUTSHEETS SUBMITTED FOR |
| | BACKFLOW PREVENTER, FIRE SPRINKLERS, PIPING, HANGERS, |
| | ETC. |
| | |
| | NEW COMMENT: PART OF THE ROOFING STRUCTURE IS |
| | CONSTRUCTED OF COMBUSTIBLE CONSTRUCTION; HOWEVER, NO |
| | SPRINKLERS HAVE BEEN PROVIDED IN THE COMBUSTIBLE |
| | CONCEALED SPACE PER NFPA 13. |
| | |
| | NEW COMMENT: THE HYDRAULIC AREA UTILIZES A SPRINKLER |
| | AREA OF 120 SQUARE FEET PER SPRINKLER. PROVIDE |
| | HYDRAULIC CALCULATIONS UTILIZING THE NORTHEAST COOLER |
| | AS THE REMOTE SPRINKLER BECAUSE THIS SPRINKLER APPEARS |
| | TO BE PROTECTING AN AREA OF 182 SQUARE FEET, THEREBY |
| | REQUIRING A STARTING FLOW OF +36 GALLONS (182 X 0.2 |
| | DENSITY). |
| | |
| | NEW COMMENT: THE HYDRAULIC AREA SUPPORTS THE USE OF 4 |
| | SPRINKLERS SUPPLIED FROM AN 1-1/4" BRANCHLINE; HOWEVER, |
| | A COUPLE OTHER BRANCHLINES HAVE MORE THAN FOUR |
| | SPRINKLERS ON THE BRANCHLINE IN THE SAME SIZE REMOTE |
| | AREA. PROVIDE A HYDRAULIC CALCULATION FOR THE SOUTHWEST |
| | KITCHEN AREA. |
| | |