2017-02-15 15:25:355011 BROADWAY - CITY MARKET
 PERMIT #17010063
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REVISE PERMIT VALUE: UNDERGROUND FIRELINE AND BACKFLOW
 PREVENTER VALUE NEEDS TO BE ADDED TO THE FIRE SPRINKLER
 PERMIT SO THE PROPER FEES CAN BE ASSESSED. ORIGINAL
 COMMENT - SHEET FP1: PLANS INDICATE 4-INCH UNDERGROUND
 FIRE MAIN IS TO BE INSTALLED BY OTHERS. IS THIS
 CORRECT? IF YES, A SEPARATE UNDERGROUND FIRE LINE
 PERMIT WILL BE NEEDED.
  
 REPEAT COMMENT: NO EQUIPMENT CUTSHEETS SUBMITTED FOR
 BACKFLOW PREVENTER, FIRE SPRINKLERS, PIPING, HANGERS,
 ETC.
  
 NEW COMMENT: PART OF THE ROOFING STRUCTURE IS
 CONSTRUCTED OF COMBUSTIBLE CONSTRUCTION; HOWEVER, NO
 SPRINKLERS HAVE BEEN PROVIDED IN THE COMBUSTIBLE
 CONCEALED SPACE PER NFPA 13.
  
 NEW COMMENT: THE HYDRAULIC AREA UTILIZES A SPRINKLER
 AREA OF 120 SQUARE FEET PER SPRINKLER. PROVIDE
 HYDRAULIC CALCULATIONS UTILIZING THE NORTHEAST COOLER
 AS THE REMOTE SPRINKLER BECAUSE THIS SPRINKLER APPEARS
 TO BE PROTECTING AN AREA OF 182 SQUARE FEET, THEREBY
 REQUIRING A STARTING FLOW OF +36 GALLONS (182 X 0.2
 DENSITY).
  
 NEW COMMENT: THE HYDRAULIC AREA SUPPORTS THE USE OF 4
 SPRINKLERS SUPPLIED FROM AN 1-1/4" BRANCHLINE; HOWEVER,
 A COUPLE OTHER BRANCHLINES HAVE MORE THAN FOUR
 SPRINKLERS ON THE BRANCHLINE IN THE SAME SIZE REMOTE
 AREA. PROVIDE A HYDRAULIC CALCULATION FOR THE SOUTHWEST
 KITCHEN AREA.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE