Plan Review Notes
Plan Review Notes For Permit 17010057
Permit Number 17010057
Review Stop E
Sequence Number 2
Notes
Date Text
2017-01-12 14:12:26PROVISO 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] SEPERATE STRUCTURE SHALL HAVE A SINGLE BRANCH
 CIRCUIT THEREFORE MEETING THE EXCEPTION REQUIREMENTS
 NEC 250.32 (GROUNDING SEPERATE STRUCTURE). AN EGC WILL
 BE ROUTED ALONG THE CIRCUIT CONDUCTORS FOR FAULT
 PROTECTION.
  