Plan Review Notes
Plan Review Notes For Permit 17010057
Permit Number 17010057
Review Stop E
Sequence Number 1
Notes
Date Text
2017-01-05 18:05:521ST REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] CLARIFY SCOPE OF WORK, THE APPLICATION CALLS OUT FOR
 INTERIOR WIRING? THIS REQUIRES AN ELECTRICAL FLOOR PLAN
 MEETING MINIMUM PROVISIONS SUCH AS RECEPTACLE OUTLET
 SPACING, LIGHTING OUTLET IN HABITABLE ROOMS, SMOKE
 ALARMS, TAMPER-RESISTANT RECEPTACLES, & AFCI, GFCI
 PROTECTION. FBC 107 (SHOW COMPLIANCE).
  
 2] ADD AN INTERSYSTEM BONDING TERMINAL TO THE GROUNDING
 DETAIL ON RISER DIAGRAM. NEC 250.94
  
 3] THE LOAD CALCULATION ARE INADEQUATE, PLEASE REFRENCE
 NEC 220.82 (OPTIONAL) AND PROVIDE THE MINIMUM 3VA FOR
 GENERAL LIGHTING PLUS THE 2 SMALL APPLIANCE CIRCUITS
 1500VA EACH. IN ADDITION THE DEMAND PERCENTAGE IS 40%
 NOT 45% PLEASE CORRECT ACCORDINGLY.