| Plan Review Notes For Permit 17010057 |
| Permit Number |
17010057 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-01-05 18:05:52 | 1ST REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1] CLARIFY SCOPE OF WORK, THE APPLICATION CALLS OUT FOR | | | INTERIOR WIRING? THIS REQUIRES AN ELECTRICAL FLOOR PLAN | | | MEETING MINIMUM PROVISIONS SUCH AS RECEPTACLE OUTLET | | | SPACING, LIGHTING OUTLET IN HABITABLE ROOMS, SMOKE | | | ALARMS, TAMPER-RESISTANT RECEPTACLES, & AFCI, GFCI | | | PROTECTION. FBC 107 (SHOW COMPLIANCE). | | | | | | 2] ADD AN INTERSYSTEM BONDING TERMINAL TO THE GROUNDING | | | DETAIL ON RISER DIAGRAM. NEC 250.94 | | | | | | 3] THE LOAD CALCULATION ARE INADEQUATE, PLEASE REFRENCE | | | NEC 220.82 (OPTIONAL) AND PROVIDE THE MINIMUM 3VA FOR | | | GENERAL LIGHTING PLUS THE 2 SMALL APPLIANCE CIRCUITS | | | 1500VA EACH. IN ADDITION THE DEMAND PERCENTAGE IS 40% | | | NOT 45% PLEASE CORRECT ACCORDINGLY. |
|