Plan Review Notes
Plan Review Notes For Permit 17010048
Permit Number 17010048
Review Stop B
Sequence Number 2
Notes
Date Text
2017-06-15 07:40:31****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. THE SKYLIGHT WAS DESIGNED TO FBC 2010, GOVERNING
 CODE IS FBC 2014, REVISE.
  
 SEE SHEET 1 OF 13 PREPARED BY DUANE D. BOICE, PE, OTHER
 LOCATIONS - ONE IS MARKED UP BY SEOR TO BE REVISED.
  
 2. DESIGNER OF RECORD TO REVIEW PRODUCTS FOR COMPLIANCE
 WITH THE DESIGN DOCUMENTS PRIOR TO SUBMITTAL.
 SUPERIMPOSED LOADS, DESIGN PRESSURES SHOULD BE REVIEWED
 PRIOR TO SUBMISSION TO THE BUILDING DIVISION.
  
 3. THREE SETS REQUIRED FBC 107.
  
 4. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS
 FS471.
  
 5. THE SHEET REFERENCED, S102, IS PART OF A REVISION
 THAT HAS NOT YET BEEN ISSUED. UNTIL THAT SHEET IS
 ISSUED, IT IS NOT A PART OF THE PERMIT RECORD SET.
  
 IT WAS SUGGESTED (MONTHS AGO) THAT APPLICANT SUBMIT
 THAT ONE SHEET AS A REVISION.
  
 OR, GET REVISION 17020076 (MODIFICATION OF KITCHEN
 LAYOUT)ISSUED. THE REVISION HAS PASSED ALL REVIEWS
 EXCEPT FOR IMPACT FEES. BE ADVISED THAT ***NO WORK***
 UNDER THAT REVISION CAN BE INSTALLED UNTIL THE REVISION
 IS ISSUED. EITHER REQUEST TO HAVE THE REVISION REVOKED
 AND ALL INSTALLATION IS TO CONFORM TO THE PERMIT
 DOCUMENTS ISSUED TO DATE, OR ADDRESS THE IMPACT FEE
 COMMENT AND HAVE THIS REVISION ISSUED.
  
 IT IS NOT CLEAR WHY THIS HAS NOT BEEN ADDRESSED AS THE
 IMPACT FEES DUE WILL LIKELY BE MINIMAL. IT IS MY
 UNDERSTANDING THAT THE SQUARE FOOT AREA ADDED WAS LESS
 THAN 200 FEET.
  
  
  