| 2017-06-15 07:40:31 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | 1. THE SKYLIGHT WAS DESIGNED TO FBC 2010, GOVERNING |
| | CODE IS FBC 2014, REVISE. |
| | |
| | SEE SHEET 1 OF 13 PREPARED BY DUANE D. BOICE, PE, OTHER |
| | LOCATIONS - ONE IS MARKED UP BY SEOR TO BE REVISED. |
| | |
| | 2. DESIGNER OF RECORD TO REVIEW PRODUCTS FOR COMPLIANCE |
| | WITH THE DESIGN DOCUMENTS PRIOR TO SUBMITTAL. |
| | SUPERIMPOSED LOADS, DESIGN PRESSURES SHOULD BE REVIEWED |
| | PRIOR TO SUBMISSION TO THE BUILDING DIVISION. |
| | |
| | 3. THREE SETS REQUIRED FBC 107. |
| | |
| | 4. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR |
| | PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS |
| | FS471. |
| | |
| | 5. THE SHEET REFERENCED, S102, IS PART OF A REVISION |
| | THAT HAS NOT YET BEEN ISSUED. UNTIL THAT SHEET IS |
| | ISSUED, IT IS NOT A PART OF THE PERMIT RECORD SET. |
| | |
| | IT WAS SUGGESTED (MONTHS AGO) THAT APPLICANT SUBMIT |
| | THAT ONE SHEET AS A REVISION. |
| | |
| | OR, GET REVISION 17020076 (MODIFICATION OF KITCHEN |
| | LAYOUT)ISSUED. THE REVISION HAS PASSED ALL REVIEWS |
| | EXCEPT FOR IMPACT FEES. BE ADVISED THAT ***NO WORK*** |
| | UNDER THAT REVISION CAN BE INSTALLED UNTIL THE REVISION |
| | IS ISSUED. EITHER REQUEST TO HAVE THE REVISION REVOKED |
| | AND ALL INSTALLATION IS TO CONFORM TO THE PERMIT |
| | DOCUMENTS ISSUED TO DATE, OR ADDRESS THE IMPACT FEE |
| | COMMENT AND HAVE THIS REVISION ISSUED. |
| | |
| | IT IS NOT CLEAR WHY THIS HAS NOT BEEN ADDRESSED AS THE |
| | IMPACT FEES DUE WILL LIKELY BE MINIMAL. IT IS MY |
| | UNDERSTANDING THAT THE SQUARE FOOT AREA ADDED WAS LESS |
| | THAN 200 FEET. |
| | |
| | |
| | |