2017-01-24 11:20:08****CORRECTIONS****
 REVISED 1/27/17
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. THE CALCULATIONS SHOW A DP OF +30.2 / -83.6. SEE
 SHEET S102, THIS DOES NOT MEET THE MINIMUM DESIGN
 PRESSURES SPECIFIED BY THE ENGINEER OF RECORD.
  
 2. THE SKYLIGHT WAS DESIGNED TO FBC 2010, GOVERNING
 CODE IS FBC 2014, REVISE.
  
 3. DESIGNER OF RECORD TO REVIEW PRODUCTS FOR COMPLIANCE
 WITH THE DESIGN DOCUMENTS PRIOR TO SUBMITTAL.
 SUPERIMPOSED LOADS, DESIGN PRESSURES SHOULD BE REVIEWED
 PRIOR TO SUBMISSION TO THE BUILDING DIVISION.
  
  
  