| Notes |
| Date |
Text |
| 2017-01-24 11:20:08 | ****CORRECTIONS**** | | | REVISED 1/27/17 | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. THE CALCULATIONS SHOW A DP OF +30.2 / -83.6. SEE | | | SHEET S102, THIS DOES NOT MEET THE MINIMUM DESIGN | | | PRESSURES SPECIFIED BY THE ENGINEER OF RECORD. | | | | | | 2. THE SKYLIGHT WAS DESIGNED TO FBC 2010, GOVERNING | | | CODE IS FBC 2014, REVISE. | | | | | | 3. DESIGNER OF RECORD TO REVIEW PRODUCTS FOR COMPLIANCE | | | WITH THE DESIGN DOCUMENTS PRIOR TO SUBMITTAL. | | | SUPERIMPOSED LOADS, DESIGN PRESSURES SHOULD BE REVIEWED | | | PRIOR TO SUBMISSION TO THE BUILDING DIVISION. | | | | | | | | | |
|