| Date |
Text |
| 2017-12-12 10:23:50 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17010014 |
| | ADD: 820 N. TAMARIND AVE. |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: 832-4437 / GENIA BAKER |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: TUES. DEC. 12/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. SITE PLAN SUBMITTED. |
| | |
| | 2) SEMI-COMPLIED. A SITE PLAN WAS SUBMITTED, THERE IS |
| | NO DIMENSION FROM THE SIDE OF THE BUILDING TO THE |
| | PROPERTY LINE. PLEASE NOTE ON THE LEFT SIDE OF THE |
| | BUILDING THE SITE PLAN SHOWS AN EXISTING BUILDING OVER |
| | THE PROPERTY LINE BY 2 FEET. WHEN YOU GO TO THE PALM |
| | BEACH COUNTY PROPERTY APPRAISERS AERIALS THE STRUCTURE |
| | THAT WAS OVER THE PROPERTY LINE HAS BEEN DEMOLISHED, |
| | PLEASE UPDATE THE SITE PLAN. 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED. 2014 EXISTING BUILDING CODE |
| | 1012.6.2 EXTERIOR WALL RATING FOR CHANGE OF OCCUPANCY |
| | CLASSIFICATION TO AN EQUAL OR LESSER HAZARD CATEGORY. |
| | WHEN A CHANGE OF OCCUPANCY CLASSIFICATION IS MADE TO AN |
| | EQUAL OR LESSER HAZARD CATEGORY AS SHOWN IN TABLE |
| | 1012.6, EXISTING EXTERIOR WALLS, INCLUDING OPENINGS, |
| | SHALL BE ACCEPTED. |
| | |
| | |
| | 3)2ND REQUEST. THE EXISTING BUILDING AT THE SITE IS |
| | ADDRESSED 820 N. TAMARIND AVE. (PERMIT APPLICATION). |
| | THE PROPERTY CONTROL NUMBER LIST THE ADDRESS AS 820 N. |
| | TAMARIND, THE PLANS ARE ALL LISTED WITH 822 N. TAMARIND |
| | AVE. IS THERE A DISCREPANCY BETWEEN THE ADDRESS? |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED. |
| | |
| | 4-5) COMPLIED. ARCHITECT ELIZABETH COLOME, SIGNED AND |
| | SEALED PLANS |
| | |
| | 6A) FLOOR LOADING. |
| | |
| | 6B) NEW COMMENT. THE BUILDING IS APPROXIMATELY 15 FEET |
| | WIDE SPAN INTERIOR WALL TO INTERIOR WALL. THE PLANS DO |
| | NOT INDICATE IF THE CEILING JOIST ARE 2 X 6 JOIST, AT |
| | WHAT CENTERS AND IF THEY ARE ONE CONTINUOUS CEILING |
| | JOIST, OR IF THEY ARE LAPPED AND NAILED AT THE CENTER |
| | OF THE BUILDING? THIS IS CRITICAL TO KNOW, IF THE |
| | CEILING JOIST ARE NOT CONTINUOUS FROM ONE EXTERIOR WALL |
| | TO THE OTHER AND THEY ARE LAPPED AND NAILED THEN A |
| | CENTER BEARING WALL OR BEAM SYSTEM WOULD BE REQUIRED TO |
| | CARRY THE CEILING LOADS. 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED. NEITHER THE ARCHITECTURAL NOR |
| | STRUCTURAL SHEETS ADDRESS THIS CONCERN. |
| | |
| | 6C) NEW COMMENT. SHEET A3 DETAIL # 3 SHOWS A EXTERIOR |
| | WALL WITH THE CEILING JOIST DROPPED TO A HEIGHT OF 7-10 |
| | AND THE TOP OF THE DOUBLE TOP PLATE AT 9-0 FEET. VERIFY |
| | IF THE TOP PLATE TO BE AT 8-0 FEET OR 9-0 FEET . FIRE |
| | STOPPING WOULD BE REQUIRED AS DEPICTED. 2014 FBC-B |
| | 718.2.1 FIREBLOCKING MATERIALS. |
| | |
| | 6D) NEW COMMENT. SHEET S2 SHOWS THE ROOF ZONE PLAN WITH |
| | A HIPPED ROOF AND IN THE ROOF AND WALL SCHEDULE FOR |
| | ALLOWABLE PRESSURES (VASD) ROOF ZONE 2 AND 3 HAVING THE |
| | SAME PRESSURES. THIS IS A TRUE STATEMENT ASCE 7-10 |
| | UNDER CHAPTER 30 ALLOWS THE PRESSURES TO BE REDUCED FOR |
| | ZONE 3 FOR FLAT ROOFS WITH PARAPETS AND OR FOR ROOF |
| | WITH HIP ROOFS. NOTE THIS STRUCTURE HAS A GABLE ROOF |
| | AND A ROOF ZONE # 3 FOR PRESSURES. |
| | THE SECOND THING WITH THE PRESSURE CHART IS THAT WE DO |
| | NOT KNOW FOR WHAT TRIBUTARY AREA THE PRESSURES ARE |
| | TAKEN, 107.2.1.3. ADDITIONAL INFORMATION REQUIRED. |
| | THE THIRD THING YOU WILL NEED TO UPDATE IS FOOTNOTE A |
| | STILL REFERENCES THE 2010 FBC-B. THE 2014 FBC-B WAS |
| | ISSUED STATE WIDE ON JUNE 30/ 2015. + |
| | |
| | 7-9)COMPLIED. |
| | |
| | 10) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 11) NO VALUE HAS BEEN PUT AGAINST THIS PERMIT FEES WILL |
| | HAVE TO BE REVISED. |
| | |
| | 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. |
| | WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |