| 2017-01-25 12:55:53 | 1ST REVIEW |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER LL |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 561-805-6711 |
| | [email protected] |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. PLEASE PROVIDE OCCUPANT LOAD FOR BUILDING. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 2. A WATER FOUNTAIN WILL BE REQUIRED IF OCCUPANT LOAD |
| | IS OVER 15. PER FBC PL TABLE 403.1 |
| | |
| | 3. A SERVICE SINK WILL BE REQUIRED IS OCCUPANT LOAD IS |
| | OVER 15. PER FBC PL TABLE 403.1 |
| | |
| | 4. SHOW CLEARANCE FOR WC SHALL COMPLY WITH FBC ACC |
| | 604.3.1 SIZE. |
| | CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES |
| | (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE |
| | WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED |
| | PERPENDICULAR FROM THE REAR WALL. |
| | |
| | 5. SHOW THE HIGHT OF TOILET SEAT. PER FBC ACC 604.4 |
| | SEATS. |
| | THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH |
| | FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES |
| | (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS |
| | SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION. |
| | |
| | 6. SHOW GRAB BARS COMPLIANCE WITH FBC ACC 604.5.1 SIDE |
| | WALL. |
| | THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM) |
| | LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM |
| | THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM |
| | FROM THE REAR WALL. |
| | |
| | 604.5.2 REAR WALL. |
| | THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG |
| | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER |
| | CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24 |
| | INCHES (610 MM) MINIMUM ON THE OTHER SIDE. |
| | |
| | 609.4 POSITION OF GRAB BARS. |
| | GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION, |
| | 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM) |
| | MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF |
| | THE GRIPPING SURFACE |
| | |
| | 7. THE TOILET PAPER DISPENSER SHALL COMPLY WITH FBC ACC |
| | 604.7 DISPENSERS. |
| | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| | SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 |
| | MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| | THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE |
| | DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48 |
| | INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND |
| | SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL |
| | NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES |
| | NOT ALLOW CONTINUOUS PAPER FLOW. |
| | |
| | 8. THE OUTLET OF THE SOAP DISPENSER SHALL BE MIN 15" |
| | AND MAX OF 48" AFF. PER FBC ACC 308.2.2 |
| | |
| | 9. LAVATORY SHALL COMPLY WITH FBC PL 416.5 TEMPERED |
| | WATER FOR PUBLIC HAND-WASHING FACILITIES. |
| | TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND |
| | GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES |
| | PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED |
| | WATER SHALL BE DELIVERED THROUGH AN APPROVED |
| | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| | 1070 OR CSA B125.3. |
| | |
| | 10. IF OCCUPANT LOAD IS OVER 15 IT SHALL COMPLY WITH |
| | FBC PL 403.2 SEPARATE FACILITIES. |
| | WHERE PLUMBING FIXTURES ARE REQUIRED, SEPARATE |
| | FACILITIES SHALL BE PROVIDED FOR EACH SEX. |
| | |
| | EXCEPTIONS: 2. SEPARATE FACILITIES SHALL NOT BE |
| | REQUIRED IN STRUCTURES OR TENANT SPACES WITH A TOTAL |
| | OCCUPANT LOAD, INCLUDING BOTH EMPLOYEES AND CUSTOMERS, |
| | OF 15 OR FEWER |
| | |