| 2017-01-24 10:09:41 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17010014 |
| | ADD: 820 N. TAMARIND AVE. |
| | CONT: TBD/ CURSORY REVIEW |
| | TEL: 832-4437 / GENIA BAKER |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. JAN. 24/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE NOTE ONLY ONE SET OF PLANS SUBMITTED. 2014 |
| | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 107.2.1.3: PLEASE |
| | SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS, REVISIONS, |
| | PRODUCT APPROVALS AND OR SUBMITTALS FOR REVIEW FOR |
| | PERMIT. IF YOUR PROJECT WILL REQUIRE A RESIDENT |
| | INSPECTOR OR IF YOUR PROJECT IS A THRESHOLD BUILDING |
| | REQUIRING A THRESHOLD INSPECTOR THEN (3) THREE SETS OF |
| | ALL SAID DOCUMENTS WILL BE REQUIRED FOR PERMIT |
| | ISSUANCE. |
| | |
| | 2) THE PLANS ARE LACKING A SURVEY AND OR SITE PLAN WITH |
| | MEASUREMENTS FROM THE PROPERTY LINE. |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR |
| | BUILDINGS. |
| | 107.3.5.1.1 COMMERCIAL BUILDINGS: BUILDING |
| | SITE PLAN/ SURVEY ? SHEET A-1 THE TITLEBLOCK LIST THIS |
| | SHEET AS PLANS. |
| | |
| | 3) THE EXISTING BUILDING AT THE SITE IS ADDRESSED 822 |
| | N. TAMARIND AVE. THE PROPERTY CONTROL NUMBER LIST THE |
| | ADDRESS AS 820 N. TAMARIND, IS THERE A DISCREPANCY |
| | BETWEEN THE ADDRESS? |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED. |
| | |
| | 4) THE PLANS ARE A DESIGN BY ARCHITECT ELIZABETH COLOME |
| | ARE NOT SIGNED NOR SEALED. PLANS, SPECIFICATIONS, |
| | REPORTS OR OTHER DOCUMENTS PREPARED BY THE DESIGN |
| | PROFESSIONAL AND BEING FILED FOR PUBLIC RECORD SHALL |
| | HAVE THE SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL |
| | AFFIXED TO THE DOCUMENT. |
| | |
| | FL ADMIN CODE 61G16.003 ARCHITECTS |
| | PLANS ARE TO BE SIGNED WITH A FULL SIGNATURE FROM THE |
| | ARCHITECT OF RECORD PER 481.221 WITH A MINIMUM OF FIRST |
| | AND LAST NAME AS SHOWN ON THE ARCHITECTS' LICENSE, FAC |
| | 61G1-16.003 |
| | |
| | 5) THE PERMIT APPLICATION INDICATES THIS PERMIT WILL BE |
| | FOR A CHANGE OF OCCUPANCY. THERE IS NO BUILDING CODE |
| | CRITERIA STATED AS TO WHAT CODES THE PLANS WERE |
| | DESIGNED TOO? THE 5TH EDITION OF THE FLORIDA BUILDING |
| | FAMILY OF CODES INCLUDING THE EXISTING BUILDING CODE |
| | WERE ADOPTED STATEWIDE ON JUNE 30/ 2015. |
| | PLEASE REVIEW THE REQUIREMENTS OF THE EXISTING BUILDING |
| | CODE CHAPTER 10 FOR CHANGE OF OCCUPANCY REQUIREMENTS! |
| | 6) MISSING DESIGN CRITERIA, 2014 FLORIDA BUILDING CODE |
| | W 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.3.5 |
| | MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | 107.3.5.1.1 COMMERCIAL BUILDINGS: BUILDING: |
| | |
| | |
| | |
| | 4) THE COVERSHEET LABELED PLANS (SITE PLAN)MISSING |
| | BUILDING DESIGN CRITERIA 2014 FLORIDA BUILDING CODE W |
| | 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 107.3.5 MINIMUM PLAN |
| | REVIEW CRITERIA FOR BUILDINGS. |
| | 107.3.5.1.1 COMMERCIAL BUILDINGS: BUILDING |
| | 4.1) SITE REQUIREMENTS: |
| | PARKING PROVIDE DIMENSIONS TO CITY ZONING REQUIREMENTS |
| | ON THE SITE PLAN |
| | SET BACKS |
| | DRIVING/TURNING RADIUS |
| | ACCESSIBLE ACCESS AISLE , DIMENSIONED STRIPED |
| | ACCESSIBLE PARKING SPACE DIMENSIONED |
| | 4.2) OCCUPANCY TYPE/ CHANGE OF OCCUPANCY FROM WHAT |
| | OCCUPANCY (CHAPTER 10 OF THE 2014 EXISTING |
| | BUILDING CODE) |
| | 4.3) MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED |
| | BY FBC-B TABLE 503 |
| | 4.4) LIFE SAFETY SHALL BE DETERMINED AND SHALL INCLUDE |
| | THE FOLLOWING REQUIREMENTS: |
| | OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| | OCCUPANCY LOAD |
| | GROSS |
| | NET |
| | MEANS OF EGRESS |
| | EXIT ACCESS |
| | EXIT |
| | EXIT DISCHARGE |
| | STAIRS CONSTRUCTION/ RAMP CONSTRUCTION/ LANDINGS/ |
| | GEOMETRY AND PROTECTION |
| | DOORS |
| | EMERGENCY LIGHTING AND EXIT SIGNS |
| | 4.5) ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE |
| | FOLLOWING: |
| | SITE REQUIREMENTS |
| | ACCESSIBLE ROUTE |
| | VERTICAL ACCESSIBILITY |
| | TOILET AND BATHING FACILITIES |
| | DRINKING FOUNTAINS |
| | SIGNAGE |
| | 4.6) ENERGY CALCULATIONS |
| | |
| | 4.7 LIGHT AND VENTILATION SHOW CRAWL SPACE CROSS |
| | VENTILATION AND ACCESS |
| | |
| | 5) PLANS SHALL COMPLY WITH 2014 EXISTING BUILDING CODE |
| | SECTION 1001.3 CHANGE OF OCCUPANCY CLASSIFICATION. |
| | WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING |
| | CHANGES, THE PROVISIONS OF SECTIONS 1002 THROUGH 1012 |
| | SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY |
| | CLASSIFICATION WITHIN A GROUP AS WELL AS A CHANGE OF |
| | OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A DIFFERENT |
| | GROUP. |
| | |
| | 6) PLEASE PROVIDE HOW THE BUILDINGS FLOOR LIVE LOADS |
| | ARE GOING TO COMPLY. TRADITIONALLY SINGLE FAMILY |
| | RESIDENCES THE BEDROOMS WERE DESIGNED WITH 30 PSF LIVE |
| | LOAD AND THE REMAINDER OF THE HOUSE THE FLOOR LOADS |
| | WERE DESIGNED TO 40 PSF LIVE LOAD. THE LIVE LOADS FOR |
| | OFFICE SPACE (BUSINESS) ARE 50 PSF, AND IF RETAIL 100 |
| | PSF, SEE 2014 FBC-B TABLE 1607.1. EXISTING BUILDING |
| | CODE [B] 1007.1 GRAVITY LOADS. BUILDINGS OR PORTIONS |
| | THEREOF SUBJECT TO A CHANGE OF OCCUPANCY WHERE SUCH |
| | CHANGE IN THE NATURE OF OCCUPANCY RESULTS IN HIGHER |
| | UNIFORM OR CONCENTRATED LOADS BASED ON THE FLORIDA |
| | BUILDING CODE, BUILDING TABLE 1607.1 SHALL COMPLY WITH |
| | THE GRAVITY LOAD PROVISIONS OF THE FLORIDA BUILDING |
| | CODE, BUILDING. |
| | |
| | 7) EXISTING BUILDING CODE SECTIONS 1012.1.4 |
| | ACCESSIBILITY. ALL BUILDINGS UNDERGOING A CHANGE OF |
| | OCCUPANCY CLASSIFICATION SHALL COMPLY WITH SECTION |
| | 1012.8. |
| | 1012.8 ACCESSIBILITY. EXISTING BUILDINGS THAT UNDERGO A |
| | CHANGE OF GROUP OR OCCUPANCY CLASSIFICATION SHALL |
| | COMPLY WITH THE PROVISIONS OF THE FLORIDA BUILDING |
| | CODE, ACCESSIBILITY. |
| | |
| | 7.1 EITHER THE DESIGNER OR CONTRACTOR WILL PROVIDE THE |
| | VALUE OF THE PROJECT FOR A CHANGE OF OCCUPANCY. THEN AN |
| | ITEMIZED LIST WILL BE REQUIRED SHOWING COMPLIANCE WITH: |
| | 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF |
| | DISPROPORTIONALITY. |
| | WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH |
| | OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS |
| | DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION, |
| | THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE |
| | EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING |
| | DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE |
| | ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE |
| | ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE |
| | FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN |
| | ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST |
| | ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX |
| | RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE |
| | DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL |
| | ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND |
| | ALARMS. |
| | |
| | 101.2 EFFECT ON REMOVAL OF BARRIERS IN EXISTING |
| | FACILITIES. THIS CODE APPLIES TO ALTERATIONS TO |
| | EXISTING FACILITIES THAT ARE SUBJECT TO THE BARRIER |
| | REMOVAL REQUIREMENT UNDER TITLE III OF THE ADA TO THE |
| | EXTENT REQUIRED BY REGULATIONS ISSUED BY THE DEPARTMENT |
| | OF JUSTICE INCORPORATED IN 202.6.1 AND TO ALTERATIONS |
| | UNDERTAKEN BY TITLE II ENTITIES TO PROVIDE PROGRAM |
| | ACCESS. |
| | |
| | 7.2) AN ACCESSIBLE ENTRANCE, THE PLANS (SHEET A1) SHOW |
| | A RAMP, THEY DO NOT PROVIDE THE ELEVATION OF THE |
| | INTERIOR FLOOR, MAXIMUM THRESHOLD HEIGHT, THE EXTERIOR |
| | LANDING ADJACENT TO THE ENTRY DOOR, CROSS SLOPE, THE |
| | PLANS ARE DEFICIENT IN PROVIDING A 5-0 TURNING RADIUS |
| | INSIDE OF THE LANDING, NOR THE ELEVATION AT THE TOP OF |
| | THE RAMP, ELEVATION BOTTOM OF RAMP, DISTANCE OF SLOPED |
| | RAMP, SLOPE FOR THE ACCESSIBLE RAMP, NOR THE LENGTH OF |
| | THE BOTTOM RAMP. |
| | |
| | 7.3) AN ACCESSIBLE ROUTE TO ALTERED AREAS, SHEET A1, |
| | PLEASE REVIEW THE DETAIL FOR BOTH THE BREAK ROOM AND |
| | RESTROOM, BOTH INDICATE THE DETAILS ARE TO BE FOUND ON |
| | SHEET A-4. THERE IS NO A-4, THEY ARE FOUND ON A-3, A |
| | TYPO, 107.2.1.3 ADDITIONAL INFORMATION . |
| | |
| | 7.4 SHEET A-1 THE RESTROOM NOR A-3 THE RESTROOM DETAILS |
| | SHOW THE REQUIRED 60 INCH CLEAR SPACE REQUIRED BY |
| | ACCESS. CODE 604.3.1. |
| | |
| | 7.5)AN ACCESSIBLE RESTROOM. SHEET A-3 THE RESTROOM |
| | SHOWS THE GRAB BARS FOR THE WATER CLOSET CENTER LINED |
| | BETWEEN 33-36 INCHES. PLEASE REVIEW 609.4. UNDER THE |
| | 2014 ACCESS. CODE THE GRAB BARS ARE TO BE MEASURED FROM |
| | FINISH FLOOR TO THE TOP GRASPABLE SURFACE NOT CENTER |
| | LINED. |
| | |
| | 7.6) THE PLANS INDICATE TILE IN THE RESTROOM, WHAT TYPE |
| | OF BACKING TO BE INSTALLED. SHOW COMPLIANCE WITH FBC-B |
| | 2509.2 BASE FOR TILE. |
| | 7.7) SHEET A-3 DETAIL #5 THE BREAK ROOM SHOWS AN |
| | MICROWAVE, SHELF THE MICROWAVE SETS ON IS 4FOOT 6 |
| | INCHES ABOVE FINISH FLOOR. PLEASE PROVIDE COMPLIANCE |
| | WITH 2014 FBC-ACCESSIBILITY CODE: |
| | 308 REACH RANGES & 309 OPERABLE PARTS |
| | 309.2 CLEAR FLOOR SPACE. |
| | A CLEAR FLOOR OR GROUND SPACE COMPLYING WITH 305 SHALL |
| | BE PROVIDED. |
| | 309.3 HEIGHT. |
| | OPERABLE PARTS SHALL BE PLACED WITHIN ONE OR MORE OF |
| | THE REACH RANGES SPECIFIED IN 308. |
| | 309.4 OPERATION. |
| | OPERABLE PARTS SHALL BE OPERABLE WITH ONE HAND AND |
| | SHALL NOT REQUIRE TIGHT GRASPING, PINCHING, OR TWISTING |
| | OF THE WRIST. THE FORCE REQUIRED TO ACTIVATE OPERABLE |
| | PARTS SHALL BE 5 POUNDS (22.2 N) MAXIMUM. |
| | |
| | 7.8) (VI) WHEN POSSIBLE, ADDITIONAL ACCESSIBLE ELEMENTS |
| | SUCH AS PARKING. |
| | 2014 FBC-ACCESS. CODE 502.3 ACCESS AISLE/ 502.3.3 |
| | MARKING |
| | 2014 FBC-ACCESS. CODE ACCESSIBLE PARKING SPACE TO |
| | COMPLY WITH 502.3.3. |
| | THE METHOD AND COLOR OF MARKING ARE NOT SPECIFIED BY |
| | THESE REQUIREMENTS BUT MAY BE ADDRESSED BY STATE OR |
| | LOCAL LAWS OR REGULATIONS. BECAUSE THESE REQUIREMENTS |
| | PERMIT THE VAN ACCESS AISLE TO BE AS WIDE AS A PARKING |
| | SPACE, IT IS IMPORTANT THAT THE AISLE BE CLEARLY |
| | MARKED. |
| | |
| | 7.9 SIGNAGE: 2014 FBC-ACCESS. CODE 703.4.1 HEIGHT ABOVE |
| | FINISH FLOOR OR GROUND. TACTILE CHARACTERS ON SIGNS |
| | SHALL BE LOCATED 48 INCHES (1220 MM) MINIMUM ABOVE THE |
| | FINISH FLOOR OR GROUND SURFACE, MEASURED FROM THE |
| | BASELINE OF THE LOWEST TACTILE CHARACTER AND 60 INCHES |
| | (1525 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND |
| | SURFACE, MEASURED FROM THE BASELINE OF THE HIGHEST |
| | TACTILE CHARACTER. |
| | |
| | 8) SHEET A2 THE ELEVATIONS SHOW BOTH A HANDRAIL/ |
| | GUARDRAIL SYSTEM FOR BOTH THE LANDINGS, STAIRS AND |
| | RAMPS. THERE ARE NO DETAILS SHOWING COMPLIANCE FOR: |
| | 8.1) FBC-B 1009.7.2 RISER HEIGHT AND TREAD DEPTH. |
| | 8.2) FBC-B TABLE 1607.1 MINIMUM LIVE LOADS FOR |
| | LANDINGS, STAIRS AND RAMPS |
| | 8.3) FBC-B 1010.3 SLOPE, 1010.4 CROSS SLOPE, 1010.7 |
| | LANDINGS, &1010.7.4 CHANGE IN DIRECTION. |
| | 8.4) FBC-B 1010.11 GUARDS. GUARDS SHALL BE PROVIDED |
| | WHERE REQUIRED BY SECTION 1013 AND SHALL BE CONSTRUCTED |
| | IN ACCORDANCE WITH SECTION 1013. |
| | 8.5) FBC-B 1012.2 HEIGHT, 1012.3 HANDRAIL GRASPABILITY, |
| | 1012.4 CONTINUITY, & 1012.6 HANDRAIL EXTENSIONS. |
| | |
| | 9) PLEASE SHOW COMPLIANCE WITH THE 2014 FBC-ENERGY |
| | CODE: C401.2.1 APPLICATION TO EXISTING BUILDINGS. |
| | ADDITIONS, ALTERATIONS AND REPAIRS TO EXISTING |
| | BUILDINGS SHALL COMPLY WITH ONE OF THE FOLLOWING: |
| | |
| | 9.1. SECTIONS C402, C403, C404 AND C405; OR |
| | |
| | 9.2. ANSI/ASHRAE/IESNA 90.1. |
| | |
| | 10) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |