| 2017-01-25 11:31:34 | 1ST REVIEW |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER LL |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 561-805-6711 |
| | [email protected] |
| | |
| | PLUMBING COMMENTS: 2ND REQUEST |
| | |
| | 1. BATH # 1 ELEVATIONS BATH#2 MIRRORED PER FBC ACC |
| | 603.3 MIRRORS. |
| | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL |
| | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES |
| | OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE |
| | OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM |
| | ABOVE THE FINISH FLOOR OR GROUND. |
| | 604.5.2 REAR WALL. |
| | THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG |
| | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER |
| | CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24 |
| | INCHES (610 MM) MINIMUM ON THE OTHER SIDE. |
| | |
| | |
| | |
| | 1. THE 3 COMPARTMENT SINK , FLOOR DRAIN AND TABLE SINK |
| | AND SLOPE SINK ARE REQUIRED TO CONNECT TO A GREASE |
| | INTERCEPTOR. PER FBC PL 1003.1 |
| | |
| | 2. THE FLOOR DRAIN SHALL BE EQUIPPED WITH A TRAP |
| | PRIMER. FBC PL 1002.4 |
| | |
| | 3. THE WASHING MACHINE IS REQUIRED TO DRAIN THROUGH A |
| | LENT INTERCEPTOR. PER FBC PL 1003.6 LAUNDRIES. |
| | LAUNDRY FACILITIES NOT INSTALLED WITHIN AN INDIVIDUAL |
| | DWELLING UNIT OR INTENDED FOR INDIVIDUAL FAMILY USE |
| | SHALL BE EQUIPPED WITH AN INTERCEPTOR WITH A WIRE |
| | BASKET OR SIMILAR DEVICE, REMOVABLE FOR CLEANING, THAT |
| | PREVENTS PASSAGE INTO THE DRAINAGE SYSTEM OF SOLIDS 1/2 |
| | INCH (12.7 MM) OR LARGER IN SIZE, STRING, RAGS, BUTTONS |
| | OR OTHER MATERIALS DETRIMENTAL TO THE PUBLIC SEWAGE |
| | SYSTEM. |