| Plan Review Notes For Permit 16120999 |
| Permit Number |
16120999 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-01-03 08:23:20 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FROM THE PRODUCT APPROVAL (NOA NO. 14-1030.02) FOR | | | THE GAF RUBEROID MODIFIED BITUMEN ROOF SYSTEM THAT WAS | | | SUBMITTED, SPECIFY THE SYSTEM TYPE, THE FASTENING | | | OPTION AND THE MAXIMUM DESIGN PRESSURE. THE MAXIMUM | | | DESIGN PRESSURES LISTED IN THIS NOA DO NOT MEET THE | | | REQUIRED UPLIFT PRESSURES FOR THE PERIMETER AND CORNER | | | AREAS. SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117 | | | CALCULATIONS FOR ENHANCED FASTENING FROM A FLORIDA | | | REGISTERED PROFESSIONAL ENGINEER, REGISTERED ARCHITECT | | | OR REGISTERED ROOF CONSULTANT AS REQUIRED BY LIMITATION | | | NUMBER 7 ON PAGE 30 OF THE PRODUCT APPROVAL. FBC | | | 107.2.1.3 | | | | | | | | | |
|