| 2017-01-04 09:38:17 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #16120977 | | | NATIONALS KITCHEN HOODS | | | 1/4/17 | | | | | | 1) MANY OF THE PLAN SHEETS LISTED IN THE SUMMARY | | | INFORMATION SHEET WERE NOT UPLOADED FOR REVIEW: | | | | | | A) HOOD #1122: SHEET M2.134. | | | | | | B) HOOD #122: SHEET M2.113. | | | | | | C) HOODS #447, 466, 487, 534, 58: SHEET M2.122. | | | | | | 2) HOOD #33: EXHAUST FAN SPECS NOT UPLOADED. | | | | | | 3) UPLOADED SHEETS M2.112 & M2.125 INIDCATE "SELKIRK" | | | GREASE EXHAUST DUCTWORK, HOWEVER THE SHOP DRAWINGS FOR | | | HOOD #846 INDICATE 16 GAUGE BLACK STEEL. PLEASE NOTE | | | THAT NO OTHER UPLOADED SHOP DRAWING FOR EITHER THE | | | NATIONALS OR THE ASTROS PROVIDE ANY DUCT | | | SPECIFICATIONS. PLEASE PROVIDE SPECIFICATIONS ON ALL | | | SHOP DRAWINGS. | | | | | | 4) HOOD #846: THE DUCT SIZES IN THE SHOP DRAWINGS DON'T | | | MATCH THE SIZES LISTED IN THE SUMMARY SHEET. | | | | | | 5) HOOD #534: I COULD NOT LOCATE THE 30X16" MAKEUP AIR | | | DUCT IN THE SHOP DRAWINGS. | | | | | | 6) NONE OF THE FOOD SERVICE DRAWINGS LISTED IN THE | | | SUMMARY SHEET WERE UPLOADED. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|