Plan Review Notes For Permit 16120977
Permit Number 16120977
Review Stop M
Sequence Number 1
Notes
Date Text
2017-01-04 09:38:171ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16120977
 NATIONALS KITCHEN HOODS
 1/4/17
  
 1) MANY OF THE PLAN SHEETS LISTED IN THE SUMMARY
 INFORMATION SHEET WERE NOT UPLOADED FOR REVIEW:
  
 A) HOOD #1122: SHEET M2.134.
  
 B) HOOD #122: SHEET M2.113.
  
 C) HOODS #447, 466, 487, 534, 58: SHEET M2.122.
  
 2) HOOD #33: EXHAUST FAN SPECS NOT UPLOADED.
  
 3) UPLOADED SHEETS M2.112 & M2.125 INIDCATE "SELKIRK"
 GREASE EXHAUST DUCTWORK, HOWEVER THE SHOP DRAWINGS FOR
 HOOD #846 INDICATE 16 GAUGE BLACK STEEL. PLEASE NOTE
 THAT NO OTHER UPLOADED SHOP DRAWING FOR EITHER THE
 NATIONALS OR THE ASTROS PROVIDE ANY DUCT
 SPECIFICATIONS. PLEASE PROVIDE SPECIFICATIONS ON ALL
 SHOP DRAWINGS.
  
 4) HOOD #846: THE DUCT SIZES IN THE SHOP DRAWINGS DON'T
 MATCH THE SIZES LISTED IN THE SUMMARY SHEET.
  
 5) HOOD #534: I COULD NOT LOCATE THE 30X16" MAKEUP AIR
 DUCT IN THE SHOP DRAWINGS.
  
 6) NONE OF THE FOOD SERVICE DRAWINGS LISTED IN THE
 SUMMARY SHEET WERE UPLOADED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  