2017-01-04 07:14:091ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16120976
 ASTROS KITCHEN HOODS
 1/3/17
  
 1) PROVIDE GREASE DUCT SPECIFICATIONS FOR THE TYPE I
 HOODS- SECTION 506.3.1.1. PLEASE NOTE THAT SHEETS
 M2.118 AND M2.119 ARE INDICATING "SELKIRK" OR EQUAL
 TYPE DUCTWORK.
  
 2) SHEET M2.118: HOOD #213 IS MISLABELED AS #242-
 PLEASE CORRECT.
  
 3) REFER TO PAGES 5, 6 & 18 OF THE HOOD 241 MAU A-2-2
 CURB ATTACHMENT SUBMITTAL. THE UPLOADED ENGINEERING IS
 FOR THE MUA-N-2-2 WHICH IS A MAKEUP AIR UNIT FOR THE
 NATIONALS.
  
 4) PROVIDE THE NOA'S FOR THE ROOFTOP EXHAUST FANS AND
 CURBS.
  
 5) THE FOOD SERVICE DRAWINGS LISTED IN THE SUMMARY
 INFORMATION SHEET WERE NOT UPLOADED.
  